PRODUCT DATA

68-0216-2

® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. •  All Rights Reserved 

RA889A

 Switching Relay

APPLICATION

The RA889A Switching Relay provides intermediate switching 
of line- and low-voltage devices from a line- or low-voltage 
controller and is typically applied in hydronic heating systems.

FEATURES

High load switching capability.

Troubleshooting LED.

Push-to-test button.

Replaceable transformer fuse.

Long-life DC relay drive control technology.

Relay for use with external 24 Vac or 24 Vdc supply, 
with line-voltage control, or with internal 24V 
transformer supply.

One model replaces many Honeywell models. (See 
Table 1 Replacement Cross Reference.)

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information  ........................................................

2

Installation ........................................................................

3

Mounting ........................................................................... 3
Wiring ...............................................................................

4

Operation ..........................................................................

4

Checkout ..........................................................................

4

Troubleshooting  ............................................................... 4

Summary of Contents for RA889A

Page 1: ...ystems FEATURES High load switching capability Troubleshooting LED Push to test button Replaceable transformer fuse Long life DC relay drive control technology Relay for use with external 24 Vac or 24 Vdc supply with line voltage control or with internal 24V transformer supply One model replaces many Honeywell models See Table 1 Replacement Cross Reference Contents Application 1 Features 1 Specifi...

Page 2: ... closely controlled conditions and some minor differences in performance can be expected if those conditions are changed TRADELINE Model RA889A Switching Relay with 24V controller for switching one line voltage load Electrical Ratings Voltage 120 Vac 60 Hz Thermostat Heat Anticipator Setting 0 12A Transformer Ratings Primary 120 Vac 60 Hz Secondary 24 Vac 12 VA maximum 9 VA available for exter nal...

Page 3: ... supply before wiring MOUNTING In replacement applications mount the new relay in the same location as the old relay For new installations locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled Select a location that is easily accessible for installation and service NOTE To reduce the possible transformer hum and relay noise that is sometimes a...

Page 4: ...used to provide electrical isolation in low voltage circuits if powered from a 24 Vac or 24 Vdc external source connected to W T and C Fiber barriers separate line and low voltage connections CHECKOUT 1 Keep the cover on the relay during normal operation and remove only for service and checkout 2 Relay contacts require no cleaning they are arranged to close with a wiping action and are self cleani...

Page 5: ...ASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINAL 1 2 L7148A L8148A 2 1 M14301 3 3 X2 X1 N O COM L2 L1 W T R T X2 X1 N O COM L2 L1 W T R T X2 X1 N O COM L2 L1 W T R T R T W T R T W T R T W T L1 L2 COM N O X1 X2 G L2 L1 T T C1 C2 B2 B1 L1 HOT L2 PUMP PUMP PUMP T87F T87F T87F RA889A RELAY RA889A RA889A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROT...

Page 6: ...CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED 1 1 20 VA M13321 R8888 1 G RA889A R T W T TO APPROPRIATE CONNECTIONS AS REQUIRED BY THE SYSTEM H1 H2 TYPICALLY CONNECTED TO T T OF BURNER CONTROL SYSTEM ZC H1 H2 2 2 USE COPPER CONDUCTORS ONLY FOR ALL CLASS 1 CONNECTIONS USE WIRE RATED FOR AT LEAST 167 F 75 C G L2 L1 3 4 4 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIR...

Page 7: ...ED OUTPUTS X2 X1 LOW VOLTAGE CONTROLLED OUTPUT L1 L2 COM N C N O C RA889A JUMPER LINE VOLTAGE CONTROL NEUTRAL X2 X1 L1 L2 COM N C N O C RA889A NEUTRAL X2 X1 24V CONTROLLER INPUT SUPPLY R T W T R T W T 1 REQUIRED FOR OUTPUT LED OPERATION 2 FOR SERIES 10 OR OTHER HARDWIRED ELECTRONIC 3 WIRE THERMOSTATS 3 WARNING ELECTROCUTION HAZARD POWER SUPPLY CAN CAUSE SEVERE INJURY OR DEATH DISCONNECT POWER BEFO...

Page 8: ...well Plaza 155 Gordon Baker Road Sun Hung Kai Centre P O Box 524 North York Ontario No 30 Harbour Road Minneapolis MN 55408 0524 M2H 3N7 Wanchai Hong Kong Honeywell Latin American Region Honeywell Europe S A 480 Sawgrass Corporate Parkway 3 Avenue du Bourget Suite 200 1140 Brussels Sunrise FL 33325 Belgium Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Reviews: