WARNING: 

Disconnect  all  power  from  the  starter  and 

overload relay before installing,  modifying,  or  servicing. 

A VERTISSEMENT: 

Couper 

l' alimen tation 

installation,  modification,  ou  entretien. 

avant 

CAUTION: 

Before  installing  this  product  in  a  nuclear 

application, determine if it is intended for such use. 

ATTENTION: 

Avant  d'installer  le  produit  dans  une 

application nucleaire, verifier si cela est permis. 

Introduction 

The  ABB  Solid State Overload Relay  is  shown  in  Figure 

1.  The  catalog  numbers  and  electrical  specifications 

are listed in Table 1.

Replacement  Installation 

The following instructions  describe  the  installation  of a 

Solid  State  Overload  Relay  as  a  replacement  for  an 

existing overload relay on a 300-Line starter. 

1.

Disconnect all sources of power to the starter.

2. Disconnect all  control  and  power  wiring from  the

load side of the existing overload relay.

3.

Loosen,  but  do  not  remove,  the  power  terminal

screws  located  between  the  top  of  the  overload

relay and the contactor.

4. 

Remove  and  save  the  overload  relay  mounting

screw,  located  at  the  bottom  right  corner  of  the 

overload relay housing.

Catalog Number 

NEMA 

Current 

Range, 

Figure 1. Solid State Overload Relay (size 1 shown). 

5. Remove  the  overload  relay  from  the  starter

baseplate.

6. Place the Solid State Overload Relay on  the  starter

baseplate and secure it with the mounting  screw.

7. Torque  the  power  terminal  screws,  between  the

top  of  the  Solid  State  Overload  Relay  and  the 

contactor,  to  20  lb-in  to  complete  the  electrical

connections.

8. Connect  the  control  and  power  wiring  to  the

terminals  on  the  load  side  of  the  Solid  State

Overload Relay, shown in Figure 2.

9.

Reconnect power sources to the starter.

10.

Fully depress  the  blue  reset  button  on  the  Solid

State Overload Relay to insure that it is in the  reset

position.  The  yellow  trip  flag  will  be  at  its  right

position,  as illustrated in Figure 2.

Wire Size 

Max Fuse Size,  Max Breaker 

Use with 

(75

°

C, Cu 

amps  ( Class T, 

Ratings, 

ABB 

Starter Mount  Panel Mount 

Size 

amps 

only) AWG #  H,J, L, R, K) 

amps 

Contactor 

CR324CXCS  CR324CXCP 

0&l 

.4-.85 

14-8

15 

CR324CXDS  CR324CXDP 

0&1 

.8-1.7 

14-8

15 

CR324CXES 

CR324CXEP 

0&1 

1.6-3.4 

14-8

10 

15 

C:R324CXFS 

CR324CXFP 

0 & 1 

3.2-6.8 

14-8

25 

25 

CR324CXGS  CR324CXGP 

0&l 

6.5-13.5 

14-8

50 

50 

CR324CXHS  CR324CXHP 

0 & 1 

13-27*

14-8

100 

100 

CR324DXGS  CR324DXGP 

6.5-13.5 

18-4

50 

50 

CR324DXHS  CR324DXHP 

13-27

18-4

100 

100 

CR324DXJS 

CR324DXJP 

25-50

18-4

200 

200 

NOTE:  Maximum fuse and breaker sizes are intended as guidelines. Refer to NEC and local codes for proper fuse and breaker selection. 

*Size O not to exceed 18 amperes.

Table 1. Solid State Overload Relay, NEMA Sizes 0,  1 

2, catalog numbers and electrical specifications.

CR306B/C 
CR306B/C 
CR306B/C 
CR306B/C 
CR306B/C 
CR306B/C 

CR306D 
CR306D 

CR306D 

GEH

-

6430 User's Guide

Solid State Overload Relay 

NEMA Sizes 

0, 

1 & 2 