8-20 Application BE1-CDS220
State Labels
Output
Purpose Description
Label
True False
VO3
Breaker 1 close.
Close breaker if virtual control
switch is TRUE and 86 lockout is
not tripped.
CLOSE-BKR1
CLOSE
NORMAL
BESTlogic Expression: VO3=143*/IN3
VO4
Breaker 2 trip.
OUT4 contact closes if restrained
or unrestrained trip or any time
overcurrent (251P, N, or Q) trip
occurs or for control switch trip.
TRIP-BKR2-
TRIP
NORMAL
BESTlogic Expression: VO4=87RT+87UT+251PT+251NT+251QT+101T
VO5
Breaker 2 close.
Close breaker if virtual control
switch is TRUE and 86 lockout is
not tripped.
CLOSE-BKR2
CLOSE
NORMAL
BESTlogic Expression: VO5=101C*/IN3
VO6
Used to annunciate an
alarm by contact closure or
opening if any of the
conditions programmed as
a major programmable
alarm is TRUE.
OUT6 contact closes when any
programmed major alarm
condition is TRUE.
MAJOR-ALAR
ALARM
NORMAL
BESTlogic Expression: VO6=ALMMAJ
VO11 Protective trip expression.
VO11 is TRUE when any 87, 51,
151, or 251 element trips.
PROTECTIVE
TRIP
NORMAL
BESTlogic Expression: VO11=87RT+87UT+51NT+151PT+151NT+151QT+251PT+251NT+251QT
VO12
Protective pickup
expression.
VO12 is TRUE when any 87, 51,
151, or 251 element picks up.
PROT-PICKE
PU
NORMAL
BESTlogic Expression: VO12=87RPU+87UT+51NPU+251QPU
(87UT is included to trigger the fault recorder because there is no unrestrained pickup output)
VO13
Alarm to indicate that
differential cutoff switch is
in the block operation posit-
ion. This can be used as a
programmable alarm by
enabling alarm point 21.
The programmable Variable
Label will be displayed on
the alarm report when
TRUE.
VO13 is TRUE when virtual switch
243 is in the closed position.
87-BLOCKED
ACTIVE
NORMAL
BESTlogic Expression: VO13=243
VO14
Optional. Use to annunciate
an alarm when alarm point
22 is enabled.
VO14 is TRUE when IN7 is TRUE.
IN7-ALARM
ACTIVE
NORMAL
BESTlogic Expression: VO14=IN7
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......