MACROMATIC
I
INSTALLATION INSTRUCTIONS
ISO 4-CHANNEL INTRINSICALLY SAFE RELAYS
September 2018
901-0000-328
�
Potentially hazardous voltages are present. Electrical shock can cause death or serious injury.
Installation should be done by qualified personnel following all National, State & Local Codes.
Presence de tensions potentiellement dangereuses. Une decharge electrique peut causer la mort ou des blessures graves.
L'installation devrait etre effectuee par du personnel qualifie suivant tous
/es
codes nationaux, provinciaux et /ocaux.
BE SURE TO REMOVE ALL POWER SUPPLYING THIS EQUIPMENT BEFORE CONNECTING OR DISCONNECTING WIRING.
READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE.
S'ASSURER DE SUPPRIMER TOUTE ALIMENTATION ELECTRIQUE DE CET EQU/PEMENT AVANT DE BRANCHER OU DE DEBRANCHER LES CABLAGES.
LIRE LES INSTRUCTIONS AVANT D'INSTALLER OU D'UTILISER CET APPAREIL ET LES CONSERVER POUR REFERENCE ULTERIEURE.
Installation & Wiring
1. The ISO Series Intrinsically Safe relays are UL913 Listed as associated apparatus for interfacing between hazardous and safe areas. The
ISO relay must be installed in a suitable enclosure in a safe area.
2. For DIN-rail mounting, snap the relay on 35mm DIN track. For panel mounting, first remove both terminal connectors from the safe and hazardous
sides. Then, using a thumb, gently extend the two black DIN-rail clips from under the relay until they snap into place and the mounting hole on each
one is vis ble. Mount the relay to the panel using a #8 screw through the hole on each clip.
3. Connect all wires to the device per Macromatic Control Drawing ISD1A04 (on back). The safe (black) and hazardous (blue) terminal connectors
are removable for easier wiring and keyed to prevent incorrect wiring. Use #14-24 solid or stranded copper wire with a terminal tightening torque of 7 in-lbs.
If terminal connectors were removed, be sure to fully reinsert the terminal connectors into the proper color-coded receptacle on the device.
Operation
The ISO Series relay consists of four intrinsically safe inputs and corresponding electromechanical relay outputs for each. There are also nine LEDs for
status indication as defined below.
Tile ISO se11es includes fou, conf1gwat1ons provnilng support to, a 1·.,cle vanety of applications Eacll
Configuration
conf1gu
1
at1on ,s user-selecta/Jle using a 2-pos,t,on DIP s1·.1tcll easily access1/Jle on tile top of tile IYOcluct
(see D1ag,am ,,glit) Factory
s111tcll
settings 1·.111 /Je StancJa,tf Logic (STD! ancl I Jo Delay (0 S)
With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. When an input
Standard Logic,
device from the hazardous area is closed, the input LED is ON (GREEN); the corresponding output relay
No Delay
is energized and the output LED is ON (ORANGE). When the input device opens, the input LED will be
OFF; the corresponding output relay will de-energize and the output LED will be OFF.
With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. If an input
device from the hazardous area is open when input voltage is applied, the input LED will be OFF, the
Inverse Logic,
corresponding output relay will be ON and the output LED will be ON (ORANGE). When an input device
No Delay
is closed, the input LED is ON (GREEN); the corresponding output relay will de-energize and the output
LED will be OFF. When the input device opens, the input LED will be OFF; the corresponding output
relay will energize and the output LED will be ON (ORANGE).
With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. When an input
device from the hazardous area is closed, the input LED is ON (GREEN) and the corresponding output
LED will FLASH (ORANGE) for 2 seconds. Then the corresponding output relay is energized and
Standard Logic,
the output LED is ON (ORANGE). When the input device opens, the input LED will be OFF and the
2 Second Delay
corresponding output LED will FLASH (ORANGE) for 2 seconds. Then the corresponding output relay
will de-energize and the output LED will be OFF. If the input device changes state at any time during the
delay, the corresponding output relay will remain in the current state, the output LED will stop FLASHING
and the time delay will reset.
With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. If an input
device from the hazardous area is open when input voltage is applied, the input LED will be OFF, the
corresponding output relay will be OFF, and the output LED will FLASH (ORANGE). After 2 seconds,
the corresponding output relay will energize and the output LED will be ON (ORANGE). When the input
Inverse Logic,
device closes, the input LED is ON (GREEN) and the corresponding output LED will FLASH (ORANGE).
2 Second Delay
After 2 seconds, the corresponding output relay will de-energize and the output LED will be OFF. When
the input device opens, the input LED will be OFF and the corresponding output LED will FLASH
(ORANGE). After 2 seconds, the corresponding output relay will energize and the output LED will be
ON (ORANGE) If the input device changes state at any time during the delay, the corresponding output
relay will remain in the current state, the output LED will stop FLASHING and the time delay will reset
DIP Switch Settings
DELAY:0S
a
2S
LOGIC: STD
INV
DELAY:0S
Iii!
2S
LOGIC: STD
INV
DELAY:0S
m
2S
LOGIC: STD
INV
DELAY:0S
Iii
2S
LOGIC: STD
INV
Troubleshooting:
If the unit fails to operate properly, check that all connections are correct per Control Drawing ISD1A04. If the V LED flashes Red
continuously, the device has been damaged and must be replaced.
Warranty:
All catalog-listed ISO Series Intrinsically Safe Relays manufactured by Macromatic are warranted to be free from defects in workmanship or
material under normal service and use for a period of five (5) years from date of manufacture.