SETTING NOTE 1 - CT PERFORMANCE EVALUATION: SATURATION FACTOR
The secondary current delivered by a current transformer to a relay circuit is always less than the current
available from an ideal CT. The ideal, or ratio current (
I
st=IP/RCT), is reduced by the excitation current
(
I
e) to yield the actual current (
I
s). This relationship is illustrated in the CT equivalent circuit shown in
Figure D-3.
Rs
Rl
Rr
Ve
VT
Is
Ie
IP
Ist
Figure D-3. CT Equivalent Circuit
For relaying applications, the CT performance is considered acceptable if the ratio correction is less than
10%. The ratio error is defined in C57.13-1993, section 8.1.10 as
I
e/
I
s. This criterion is expressed in the
ANSI C accuracy class which is defined in the following sentence. Under steady state (symmetrical
current) conditions, the excitation current must be less than 10 amperes for a relay current of 100
amperes into the specified standard burden. Since fault currents necessarily start with some degree of
transient DC offset, good design practice requires that the ratio error remain below 10% during the initial
transient offset period, if possible, particularly when fast tripping is in effect. It has been generally
accepted that a design for a saturation factor (SF) of 0.5 or less is acceptable. The following analysis
provides two definitions of the saturation factor, using a C200 application as an example.
Saturation Factor Defined from the ANSI C Classification
In Figure D-4, the CT terminal voltage increases linearly with the secondary current along the V=ZBxl line
where ZB is the total CT burden (leads plus relays for a particular fault and connection). A terminal
voltage (VT) corresponds to the maximum fault current. This voltage is lower than the maximum voltage
(VC) that the C200 CT can support. Saturation will occur (i.e. ratio error will exceed 10%) for secondary
currents in excess of
IFs
where the corresponding terminal voltage crosses the accuracy class limit VC
(point C in Figure D-4). We can define a measure of the degree of saturation with the Saturation Factor:
IFs
IF
SF
=
By examination of triangles OAB and OCD, the same saturation factor can be expressed as
VC
VT
SF
=
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......