Up to PL e, SILCL 3, category 4 

Correct Use 

The  SR104P  2-hand  safety  relay  is  an  extremely  com-

pact,  universal  safety  two-hand  control  unit.  It 

complies with EN574, Typ III C, and is intended for use 

in safety circuits that are designed in accordance with 

EN  60204-1,  e.g.  on  presses,  punches  and  bending 

tools. Due to  the internal error monitoring, the  2-hand 

safety relay can be used, despite very compact dimen-

sions, for all applications up to the highest safety cate-

gory 4 and  PL e according to EN ISO 13849-1, SILCL 3 

according to EN 62061 or Typ III C according to EN 574.  

Features 

• 

2 safe, redundant relay outputs 

• 

Cyclical monitoring of the output contacts 

• 

Feedback loop for monitoring downstream contactors or 

expansion modules 

• 

Short circuit and earth fault monitoring 

• 

Extrem compact housing 

Function 

The  OMRON  STI  2-hand  safety  relay  SR104P  is  suitable 

for setting up and monitoring two-hand circuits and is used 

to protect the operators. Dangerous work steps can only be 

triggered when both two-hand buttons connected are ope-

rated simultaneously, i.e. within 0.5s. 
It is to be ensured a single fault or a malfunction does not 

result  in  the  loss  of  the  safety  function  and  every  fault  is 

detected by  the cyclic self-monitoring  at  the latest  prior to 

the next actuation. 
When  the  operating  voltage  is  applied  to  A1-A2  and  the 

feedback  loop  X1-X2  is  closed,  the  SR104P  is  ready  for 

use. To be able to initiate a switching operation, the output 

relays must be de-energized. The output relays only switch 

to  the  energized  position  when  the  two-hand  buttons  T1 

and T2 are operated simultaneously, i.e. within 0.5s.  

Fig. 1 Block diagram SR104P 

 

• 

It is not allowed to open the device, tamper with the device or 

bypass the safety devices.

 

• 

All relevant sefety regulations and standards are to be observed. 

• 

The overall concept for the control system in which the device 

is integrated is to be validated.

 

• 

Failure to observe the safety regulations can result in death, 

serious injury and serious damage. 

 

Installation 

As per DIN EN 60204-1, the device is intended for installa-

tion in control cabinets with a minimum degree of protection 

of  IP54.  It  is  mounted  on  a  35-mm  DIN  rail  according  to 

DIN EN 60715 TH35. 

Safety Precauti-

ons 

• 

Installation an setup are only allowed to be undertaken 

by trained personell. 

• 

The electrical connection is only allowed to be made with the 

device and wiring isolated. 

• 

The wiring must comply with the instructions in this user 

information, otherwise there is a risk that the safety function 

will be lost. 

• 

As per EN 60204-1 the device is intended for installation in 

control cabinets with a minimum degree of protection of IP54. 

Fig. 2 Installation/removal 

Electrical Connec-

tion 

• 

When the 24V version is used, a control transformer 

according to EN 61558-2-6 or a power supply unit with 

electrical isolation from the mains must be connected. 

• 

External fusing of the safety contacts (4A slow-blow or 

6A quick-action or 10A gG) must be provided. 

• 

A maximum length of the control lines of 1000 meters 

with a line cross section of 0.75 mm

2

 must not be excee-

ded. 

• 

The line cross section must not exceed 2.5 mm

2

• 

If the device does not function after commissioning, it 

must be returned to the manufacturer unopened. Ope-

ning the device will void the warranty. 

Fig. 3 Connections 

A1: 

 Power supply 

A2. 

 Power supply 

S11:  

Control line T1 

S12: 

Control line T1 

S13: 

Control line T1 

S21: 

Control line T2 

S22: 

Control line T2 

S23: 

Control line T2 

X1; X2:  Feedback loop 
13-14:   Safety contact 1 
23-24:   Safety contact 2 

(not dor plug-in terminals) 

The output relays are not switched if: 

• 

only one two-hand button is actuated or the time between the actuation of the 2 two-hand buttons is greater than 0.5s, 

• 

the feedback loop is open (fault in the external contactor), 

• 

another error (short circuit, cable break, error in the switching device) has occurred. 

When T1 and/or T2 are/is released, the output relays opens immediately. In order to trigger a new operation, both two-hand 
buttons must first be released and the feedback loop must be closed. 

Safety 

SR104P 

User Information for SR104P 

& Innovation 

Technology 