8-26 Application BE1-CDS220
State Labels
Output
Purpose Description
Label
True False
VO1
Transformer fault trip (86T for
example).
OUT1 contact closes if a
restrained, unrestrained, or
phase differential is TRUE.
TRIP_86T-O
TRIP
NORMAL
BESTlogic Expression: VO1=87RT+87UT+51NT+151PT+151NT+151QT
VO2
Transformer fault trip (86B for
example).
Trip bus breaker via lockout for
bus faults (250T w/ 18-20 cycles
delay).
TRIP-86B-O
TRUE
FALSE
BESTlogic Expression: VO2=250TQT
VO3
Breaker 2 breaker failure trip.
(86F for example)
TRUE when BFT or 62 times out TRIP-86F-O
TRUE
FALSE
BESTlogic Expression: VO3=BFT+62
VO4
Breaker 2 trip.
Trip if 87R or 87U trip output of
the phase diff. protection
function is TRUE. Or for 251
bus backup over-current trip. Or
for control switch trip. Or when
BF is initiated.
TRIP-BKR2-
TRIP
NORMAL
BESTlogic Expression: VO4=87RT+87UT+251PT+251NT+251QT+VO9+BFPU+101T
VO5
Breaker 2 close.
Close breaker if virtual control
switch is TRUE and 86T or 86B
LO is not tripped.
CLOSE-BKR2
CLOSE
NORMAL
BESTlogic Expression: VO5=101C*/IN3*/IN4
VO6
Signal relay on bus source
that is using BUS logic that a
feeder relay is out of service.
Feeder relay is out of service as
indicated by contact open from
the feeder relays.
FDR-BACKUP
BACKUP
NORMAL
BESTlogic Expression: VO6=/IN5
VO9
52b supervised breaker
failure initiate expression
Initiate BF timing (62 timer)
when 87R or 87U trip is TRUE
or when external BFI contact
(IN6) is sensed. Stop BF timing
when breaker opens (52a status
contact). Prevent initiate when
in test mode (VO15).
BFI-62
INI
NORMAL
BESTlogic Expression: VO9=87RT*IN2*/VO15+87UT*IN2*/VO15+IN6*IN2*/VO15
VO10
Current supervised breaker
failure initiate expression.
Initiate BF timing when
protective trip expression is
TRUE. Or when external initiate
contact (IN7) is sensed and any
of the fault detectors is picked
up.
BFI-BF
INI
NORMAL
BESTlogic Expression: VO10= VO11+IN7*IN7*IN7*150TQPU
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......