10-10 Human-Machine
Interface BE1-CDS220
Automatic Display Priority
If no front panel-scrolling key has been pressed for approximately five minutes, the relay automatically
switches to and displays the highest priority REPORT STATUS menu screen. In a typical application, the
user would return to the relay and prefer to see the data that is of the most interest already on the screen.
The automatic screen display follows the priority logic described in Table 10-3. For example, if a trip has
occurred, the Targets screen is the highest priority and will be displayed automatically.
Table 10-3. Automatic Screen Display Priority Status
Priority
Priority Logic
State
Screen Displayed
Data
1 Targets
active \STAT\TARGETS
Scrolling display of Target Elements and Fault
Currents.
2
Alarms active
\STAT\ALARMS
Scrolling display of Active Alarms.
3
Scrolling Screens
active
\STAT\SCRNS\SCRN
Scrolling display of User Screens programmed
with the SG-SCREEN command.
4
Scrolling Screens
disabled
\STAT\TARGETS
Default target screen showing ‘TARGETS
NONE’.
If there are no targets or alarms, then the relay will automatically scroll through the user programmable
scroll list (there is a scrolling display of up to 16 screens).
When the display is scrolling through the programmed scroll list, you can freeze the display and manually
scroll through the scroll list. Pressing the RIGHT or LEFT scroll pushbutton will freeze the display.
Repeatedly pressing the RIGHT scroll pushbutton will progress through the scroll list in ascending order.
Repeatedly pressing the LEFT scroll pushbutton will progress through the scroll list in descending order.
Pressing the UP scroll pushbutton will leave the automatic scroll list and place you in the menu tree at
Screen 1.3, STAT\SCREENS.
Once the user has taken manual control of the display by pressing any of the scrolling pushbuttons,
automatic priority has been disabled until the display times out. Thus, if a trip or alarm occurs during this
time, the trip or Alarm LED will light up but the display will not jump to the appropriate screen. It will be
necessary to manually scroll to the Targets or Alarms screen to see this data and to reset it.
The HMI can be returned to automatic priority immediately without waiting for the timer to time out by
scrolling to Screen 1.3, STAT\SCREENS and pressing the DOWN scroll pushbutton to return to the
automatic scroll list.
Setting the Screen Scroll list
The default screen number is the screen number displayed in the upper-left-hand corner of display screen
shown in Figures 10-3 through 10-9. Consult these Figures for assistance when making or interpreting
scrolling screens settings.
The default scrolling screens are:
SG-SCREEN1 = 1.4.6
SG-SCREEN2 = 3.1.1
SG-SCREEN3 = 3.1.1.1
SG-SCREEN4 = 3.1.1.2
SG-SCREEN5 = 3.1.2
SG-SCREEN6 = 3.1.2.1
SG-SCREEN7 = 3.1.2.2
SG-SCREEN8 = 0
SG-SCREEN9 = 0
SG-SCREEN10 = 0
SG-SCREEN11 = 0
SG-SCREEN12 = 0
SG-SCREEN13 = 0
SG-SCREEN14 = 0
SG-SCREEN15 = 0
SG-SCREEN16 = 0
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......