4-20 Protection
and
Control BE1-CDS220
Table 4-9. Operating Settings for Neutral Differential
Setting
Range
Increment
Unit of Measure
Default
Minimum
Pickup
(minpu)
0 = Disabled
0.10-1.00
0.01 Times
tap
0
Slope 15-60
1
% I operate vs.
restraint
20
50-999 ms
1 m
Milliseconds
0.05 - 60 sec
0.1 for 0.1 - 9.9 s
1.0 for 10 - 60 s
Seconds
Time Delay
0 - 3600 (60 Hz) or 0 - 2500 (50 Hz)
∗
Cycles
500
∗
Time delays less than 10 cycles can be entered to the nearest 0.1 cycles from the optional HMI. All time
delays can be entered to the nearest 0.01 cycles from the ASCII command interface. Time delays entered
in cycles are converted to milliseconds or seconds. Increment precision after conversion is limited to that
appropriate for each of those units of measure.
The 87ND neutral differential operational settings may be entered with BESTCOMS (Figure 4-17), or from
the optional front panel HMI from Screens 5.#.2.1, \PROT\SG#\87ND7\87ND, or from the ASCII
command interface using the S<g>-87ND command.
Figure 4-17. Percentage Differential Screen, 87ND/187ND Tab
Retrieving Neutral Differential Status from the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT command. See Section 6, Reporting and Alarm Functions, General Status Reporting, for more
information.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......