6-44
Reporting and Alarm Functions
BE1-CDS220
The RA (report alarms) command can be used to read detailed alarm reports and reset latched alarms.
RA Command
Purpose:
Report/Reset Alarm information
Syntax:
RA[=0]
Comments:
type = LGC (Logic), MAJ (Major), MIN (Minor) or REL (Relay). <=0> means clear the
latched alarm. Privilege G or R password access is required to reset alarms.
RA Command Examples:
Example 1.
Read the current alarm status.
>RA
RA-LGC NONE
RA-MAJ NONE
RA-MIN ALARM# 16 - SETTING CHANGE
RA-REL NONE
Example 2.
Clear the latched minor alarm.
>RA-MIN=0
Links between Programmable Alarms and BESTlogic
Several links between the programmable alarms and BESTlogic allow alarm functions to be used in the
logic scheme and programmable logic functions to be used in the alarm reporting function.
Programmable Alarms Controlled by BESTlogic Elements
Virtual Outputs VO13, VO14, and VO15 are driven by BESTlogic expressions and are available in the
programmable alarms function. These three virtual outputs have labels that can be assigned meaningful
names. Then, when a logic condition that is used for an alarm exists, the label will be reported in the
alarm reporting function.
Programmable Alarms Reset
Programmable alarms can be reset by any one of three methods:
•
The programmable alarms reset logic expression becomes TRUE.
•
Pressing the front panel Reset key when HMI Screen 1.2, \STAT\ALARMS is active.
•
By connecting the alarms reset logic in BESTCOMS. Alternately, this can be done using the SA-
RESET ASCII command.
To reset the alarms using BESTCOMS select Reporting and Alarms from the Screens pull-down menu.
Then select the Alarms tab. Select the Logic button in the BESTlogic box on the right side of the screen.
Refer to Figure 6-24. The BESTlogic Function Element screen for Alarm Reset Logic will appear. See
Figure 6-27.
To connect the function's input, select the Reset button in the BESTlogic Function Element screen. The
BESTlogic Expression Builder screen will open. Select the expression type to be used. Then, select the
BESTlogic variable, or series of variables to be connected to the input. Select Save when finished to
return to the BESTlogic Function Element screen. For more details on the BESTlogic Expression Builder,
see Section 7, BESTlogic Programmable Logic. Select Done when the settings have been completely
edited.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......