8-48 Application BE1-CDS220
Table 8-30. MOTOR Output Logic
State Labels
Output
Purpose Description
Label
True False
VOA
Relay Trouble alarm.
OUTA contact closes when relay
trouble alarm occurs.
RELAY-TROU
ALARM NORMAL
BESTlogic Expression: VOA=0
VO1 Breaker
trip.
TRUE when protective trip
expression is TRUE.
MOTOR_ TRIP
TRIP
NORMAL
BESTlogic Expression: VO1=VO11
VO4
Overload alarm output
contact.
Overload protection (51P) is picked
up and timing to trip.
OVERLOAD-O
ALARM NORMAL
BESTlogic Expression: VO4=VO14
VO5
Unbalance alarm output
contact.
Unbalance protection (51Q) is
picked up and timing to trip.
UNBALANCE-
TRIP
NORMAL
BESTlogic Expression: VO5=VO15
VO7
Intermediate logic variable
that determines if a high
inertia motor application is
starting. (Not yet up to
speed).
SW 143 selects whether starting is
determined by monitoring speed
switch or current. TRUE if motor
energized 250TPPU and speed
switch (IN2) closed. Or, 50TP is
picked up. Used to unblock 151P
for Locked Rotor protection.
STARTING-H
TRUE
FALSE
BESTlogic Expression: VO9= IN2*250TPPU*143+50TPPU*/143
VO8
Intermediate logic variable
that determines if the motor
is starting. (Time set for
about 120% of maximum
start time).
TRUE if 250TP is picked up but not
yet timed out. Used to unblock jam
(251P) protection.
STARTING
TRUE
FALSE
BESTlogic Expression: VO10=250TPPU*/250TPT
VO9
Emergency Trip
intermediate logic
expression for external trip
alarm seal-in.
TRUE if IN3 is energized causing a
trip or if emergency trip alarm point
is TRUE.
EMER-TRIP-
TRUE
FALSE
BESTlogic Expression: VO9=IN3+VO13
VO11 Protective trip expression.
Restrained diff trip, 50TN ground
fault, 50TQ loss of phase, 150TP
low inertia locked rotor, 51P
overload, 51Q unbalance, 151P
high inertia locked rotor, 251P Jam,
or VO13 Emergency Trip.
PROTECTIVE
TRIP
NORMAL
BESTlogic Expression: VO11=87RT+50TNT+50TQT+51PT+51QT+151PT+251PT+VO13
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......