8-40 Application BE1-CDS220
State Labels
Output
Purpose Description
Label
True False
VO1
Bus fault trip (86B for
example).
Trip if bus fault by restrained
differential trip or for high speed
bus OC trip (50T) and not in
feeder backup mode (VO14).
TRIP-86B-O
TRIP
NORMAL
BESTlogic Expression: VO1=87RT+VO8*/VO14
VO3
Feeder breaker trip.
Trip feeder breaker via auxiliary
re-lay (94) for 50/51 (VO9) trip
when in feeder relay backup
mode (VO14).
FEEDER-BKR
TRIP
NORMAL
BESTlogic Expression: VO3= VO9*VO14
VO4
Breaker 1 trip.
Trip for bus diff, 87 is TRUE. Or,
high speed bus OC with
interlock, 50T, or bus time OC
trip, 51 is TRUE and not in
feeder backup mode (VO14).
Or, for 150T & 151 bus backup
overcurrent trip. Or, for control
switch trip.
TRIP-BKR1-
TRIP
NORMAL
BESTlogic Expression: VO4=87RT+VO9*/VO14+VO10+101T
VO5
Breaker 1 close.
Close breaker 1 (main) if virtual
control switch is TRUE and 86T
or 86B LO is not tripped.
CLOSE-BKR1
CLOSE
NORMAL
BESTlogic Expression: VO5=101C*/IN3*/IN4
VO6
Breaker Failure Initiate
output. Initiate breaker failure
protection in relay using
backup logic.
Initiate breaker failure if BFI
expression is TRUE (VO7) and
not in test mode.
BFI-OUT6
INI
NORMAL
BESTlogic Expression: VO6= VO7*/VO15
VO7
Breaker failure initiate
expression.
Initiate breaker failure for all bus
breaker protective tripping
elements. 87RT, 50/51 (when
not in feeder backup mode), or
150/151. (101T is excluded).
BFI
INI
NORMAL
BESTlogic Expression: VO9=87RT+VO9*/VO14+VO10
VO8
Intermediate logic
expression for 50T Trip.
Used for high speed bus OC
trip in normal mode or feeder
breaker inst. trip in feeder
backup mode.
TRUE if any 50T with feeder
pickup interlock is TRUE.
Elements have 2-4 cycles delay
due to interlock with feeder relay
pickups.
50T-INTERL
TRIP
NORMAL
BESTlogic Expression: VO10=50TPT+50TNT+50TQT
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......