BE1-CDS220
Testing And Maintenance
13-9
Before testing each protection and control function, the logic settings should be examined to determine:
•
The mode setting for the function so that you know what the relay is supposed to do.
•
Which virtual output logic expressions contain the logic variables that represent the outputs of the
function under test so that the proper contact can be monitored.
•
The input logic expressions for the function under test (especially the block input because it
renders the function disabled if the block input is asserted).
•
That the fault reporting settings are properly set such that the relay properly indicates pickup and
trip states and records targets. These settings are set from the ASCII command interface using
the SG-TRIGGER and SG-TARG setting commands. See Section 6, Reporting and Alarm
Functions, Fault Reporting Functions, for more details.
Testing Phase Differential Protection with Internal Compensation
The internal phase and zero sequence compensation features of the relay can combine the currents from
multiple CT input circuits and/or subtract out the zero sequence components before their use by the phase
differential function. Thus, the testing of this function with the internal compensation features can be
somewhat complicated. For this reason, a detailed test procedure is provided for verifying the set points of
this function with internal compensation. See Sidebar 13-1 in this Section for more information on how the
internal compensation features work.
Step 1.
Record settings for the following tests.
The settings for the following tests should be recorded before starting the test. You will refer to these
settings throughout the test procedure.
•
Angle Compensation and Ground Source compensation can be determined by matching the SG-
CT or Screen 6.3.1.1 settings with Table 3-2 in Section 3 and reading the right two columns to
determine what angle compensation is applied.
•
Tap Compensation settings in each setting group can be determined from screens 5.x.1.2 or
5.x.1.3 on the optional HMI. Or, the S#-TAP87 settings from the ASCII command interface if
manual tap adjust is used. If automatic tap adjust is used, it will be necessary to use the settings
and equations 4-1 and 4-2 from Section 4, Protection and Control Functions, Differential
Protection.
•
Restrained Minimum Pickup, Slope, and Unrestrained Pickup settings can be determined from
screens 5.x.1.1 on the optional HMI. Or, the S#-87 settings from the ASCII command interface.
Alternatively, all of these parameters can be determined from reading the Current Check Record provided
by the Differential Alarm Function. To use this method, use the commands in Table 13-6.
Table 13-7 lists the currents that will be seen by each 87 phase differential element after phase and zero
sequence compensation. This table is based upon the internal compensation chart in Section 3, Input and
Output Functions, Input Current. Examination of this table shows that for most cases, test current injection
using only one or two current sources will result in currents being applied to more than one 87 Phase
element. See Sidebar 13-1 for more information on testing and compensated currents. The following test
procedures will enable you to determine the test points and which phases will be tested.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......