13-34
Testing And Maintenance
BE1-CDS220
Sidebar 13-3. Maximum Restraint Operating Characteristic – Continued
Under test and in-service conditions, the following equations determine whether the relay operates
along the flat minimum pickup or slope of the operating characteristic. If:
I
restraint at balance
> minpu x
−
1
100
/
slope
1
in per unit, use Equation 1, or if
I
restraint at balance
< minpu x
−
1
100
/
slope
1
in per unit, use Equation 2.
Example (Increasing One Input from Balance):
TAP 1 = 2.00 Minpu = 0.30
TAP 2 = 3.80 Slope = 15%
Input 1 current at balance = 3 per unit (6 amperes)
Input 2 current at balance = 3 per unit (11.40 amperes)
Input 1 is being increased relative to a fixed input 2 current. Thus, the maximum restraint used by the
relay is input 1, the larger of the two currents in per unit.
I
restraint at balance
= 3 > 0.3
−
1
15
.
0
1
= 1.70 per unit
Then,
I
1trip
= I
1balance
/(1-(
100
slope
))
= 3/(1-0.85) = 3.53 per unit (see the following figure)
1
2
3
4
5
MAXIMUM RESTRAINT CURRENT (IN MULTIPLES OF TAP)
OP
ERAT
IN
G
C
U
R
R
E
N
T (I
N
MU
LT
IPLE
S
O
F
T
AP)
12
3
Slope =
I
OP
*100/I
RESTR
= 15%
minimum pickup
= 0.30 x tap
Differential current
3.53
Maximum Restraint Characteristic Example
You may also use the maximum restraint operating characteristic and test the relay by decreasing one
current from a balanced condition. For additional information on testing in this manner, see Sidebar 13-4.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......