BE1-CDS220 Settings
Calculations
D-9
Step 2:
Choose slope setting S. The tripping slope S must be greater than S
i
to provide a safety
margin at the differential tripping characteristic knee point (intersection of the minimum pickup
tripping characteristic and the slope tripping characteristic). This safety margin is required to
accommodate the additional mismatch caused by the excitation current and the unmonitored
load current. Refer to Figure D-2. A slope margin of 10% is recommended.
S = S
i
+ Slope Margin
S = 29% + 10% = 39%
Equation D-17
Step 3:
Calculate Offset Current I
offset
. The margin at the knee point of the tripping characteristic is
illustrated in Figure D-2. The additional mismatch caused by excitation current and
unmonitored loads does not vary with through current loading so it tends to offset the
operating slope S
i
upward from the origin. Thus, it decreases the safety margin at the
differential tripping characteristic knee point (intersection of the minimum pickup tripping
characteristic and the slope tripping characteristic).
unmon
offset
I
IE
I
+
=
24
.
0
0
24
.
0
=
+
=
offset
I
Where:
IE is assumed to be less than 4% of the self cooled rating.
d
forcecoole
selfcooled
X
selfcooled
MVA
MVA
IE
IE
∗
∗
=
Equation D-18
024
.
0
20
12
1
04
.
0
=
∗
∗
=
IE
Equation D-19
Where:
X is the tap conversion factor defined in Calculate Minpu, Step 1, Equation D-6.
I
unmon
is the unmonitored load calculated in Calculate Minpu, Step 2, Equation D-7.
Step 4:
Calculate Operating Margin M
o
. The Operating Margin M
o
is given by Equation D-20.
offset
i
o
I
S
S
M
−
=
-
1
Minpu
Equation D-20
The conservative calculation of margin at the knee point uses S
i
as calculated in Calculate Slope, Step 1.
For this example, M
o
in times tap is Equation D-21.
tap
times
040
.
0
024
.
0
39
29
1
25
.
0
=
−
−
∗
=
o
M
Equation D-21
The above calculation of margin is conservative. For the low current level where the margin at the tripping
characteristic knee point is of interest, the CT error will typically be less than 1%. Thus, calculating the
margin using S
i
= 20 (replace 10% CT error with 1% CT error) yields the following result in Equation D-22.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......