BE1-CDS220 Terminal
Communication
C-3
a. Using Figure C-4 as a guide, make the
following selections in the dialog box:
Check the Line Wrap and Local Echo
boxes to enable these functions.
Disable (uncheck) the CR ->CR/LF
Outbound function.
b. Set
the
Buffer Lines at 244.
c. Click
“OK”.
Step 4: Select Settings/Text Transfers.
a. Make the following selections using
Figure C-5 as a guide:
Set
Flow Control at Line at a Time.
Enable Delay Between Lines and set the
delay at 1/19 or 2/10 seconds.
Disable
Word Wrap…
b. Click
“OK”.
Step 5: Select Settings/Communications.
a. Make the following changes using Figure
c-6 as a guide:
Under
Connector, select the
appropriate communication port for
your computer.
Adjust the Baud Rate setting so that
it matches the setting of the relay.
The default baud rate of the BE1-
CDS220 is 9,600.
Set the Data Bits at 8.
Set the Stop bits at 1.
Disable Parity Check by selecting
NONE.
Set Flow Control to Xon/Xoff.
b. Click “OK”.
Step 6: Click File/Save. Enter a desired file name
such as CDS220.trm. For future
communication sessions, click File and open
this file. Terminal will automatically be setup
properly to communicate with the BE1-
CDS220.
Step 7: Terminal is now ready to communicate with
the relay.
Figure C-4. Terminal Preferences Dialog Box
Figure C-5. Text Transfers Dialog Box
Figure C-6. Communications Dialog Box
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......