13-24
Testing And Maintenance
BE1-CDS220
3.
There is a problem with the settings or installation and the initial loading is great enough to cause a
differential alarm but not a trip.
NOTE
If the load picked up results in differential current greater than the alarm set point
(scenario 3), a record will be generated automatically by the differential alarm function. If
this occurs, it is still recommended to manually trigger generation of a new differential
check record so that you are assured that you are looking at up-to-date data.
4.
There is a problem with the settings or installation and the initial loading is great enough to cause a
trip.
NOTE
If the load picked up results in a trip (scenario 4), examine the fault summary and
oscillography records to determine the cause of the trip. If it is not a fault, re-energize the
transformer and pick up less load; or, block the differential trip, re-energize the
transformer, and pick up the load. After the load is picked up, trigger a differential check
record. Once the problem has been corrected, unblock the differential element. Or, an
Exel spreadsheet template (CDSFAULT.xlt) is available from the web site
www.basler.com
. The magnitude and angle of the currents recorded in the fault summary
report at the time of the trip can be entered into this spreadsheet along with the pertinent
differential and connections settings. The spreadsheet will then calculate the differential
currents after compensation which makes it easier to diagnose and correct the problem.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......