6-32
Reporting and Alarm Functions
BE1-CDS220
A logic input can be used to reset the target. Using BESTCOMS, select Reporting and Alarms from the
Screens pull-down menu. Then select Fault Recording tab. The logic input can be connected by selecting
the Logic button in the Target Reset pane. When the logic input becomes TRUE, the target is reset.
BESTCOMS can also be used to review targets and alarms after an operation by selecting Metering from
the Reports pull-down menu. This screen (Figure 6-19) will contain target and alarm information.
Figure 6-19. BESTCOMS Metering Screen
Table 6-17 provides the possible targets that may be displayed on the Metering screen.
Table 6-17. Targets as Displayed
IEEE Device Number
Definition
50/150/250 ABC, N, Q
Instantaneous Overcurrents
51/151/251 ABC, N, Q
Time Overcurrents
BF Breaker
Failure
62/162 Logic
Timers
87R ABC
Phase Differential Restrained
87U Phase
Differential
Unrestrained
87ND
Neutral Differential Restrained
The RG-TARG (report general, targets) command can be used to read and reset the targets. Write
access to Reports must be gained to reset the targets using the ASCII command interface.
RG-TARG Command
Purpose:
Report/Reset Target status
Syntax:
RG-TARG
RG-TARG Command Example:
Example 1.
Read the targets from the ASCII command interface when the instantaneous overcurrent
elements (50 and 150), phase A and Neutral logged targets.
>RG-TARG
50AN; 150AN
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......