background image

TECHNICAL DATA

1. Current and Time Adjustments

    

     

 Earth-fault Low-set Current (I>) Adjustment

      - This adjustment is for setting the minumum earth-fault  

        current for tripping with time delay. 

      - The setting range is between 0.1A to 2A

      Earth-fault High-set Current (I>>) Adjustment

      - This adjustment is for setting the instantaneous tripping    

        current due to an earth-fault.

      - The setting range is between 1x to 10x of the earth-fault  

        low-set setting value.

 

 

I>> = a x I>  

(a= 1 to 10)

      - This high-set feature can be disabled by setting the  

         tripping current to infinity (∞).

      Time Delay (TM) Adjustment

      - The time multiplier is for setting the normal inverse  

         time/ current characteristic (IDMT) as according to  

         BS142. 

      - The setting range between 0.05 to 1.0 .

2. Light Indicators

    

     

 The light indicators display the status of the system.

AUX

I>

I>>

Off

Off

Off

No auxiliary power supply.

On

Off

Off

System normal mode. No tripping.

On

Blink 

Off

Earth-fault low-set start.

On

On

Off

Earth-fault low-set tripped.

On

Off

Blink

Earth-fault high-set start.

On 

Off

On

Earth-fault high-set tripped.

Indicator

Status

3. Push Buttons

       Reset Button

       - The reset button is for resetting the light indicators (I> or I>>) after an earth-fault tripping  

         has occured.

       - To reset, press the reset button once.

       Test  Button

       - Test button is for checking the relay operation.

       - Push and hold the test button, I> and I>> LEDs start blinking then LEDs turn On and relay  

         contacts will be activated after 3s.

4. Trip Contacts

       There are two set of tripping contacts namely, R1 and R2.

 

      R1,R2 - Manual Reset Type

      - These contacts is activated during an earth-fault trip.  The contacts remain activeted    

        regardless of the removal of fault current.  This relay can only be reset by pressing the    

        “RESET” button.

N202 IDMT Earth-Fault Relay User’s Guide

AUX

I>>

I>

TEST

RESET

0.1A 

0.5A 

2A 

1.5A 

1A 

TM

0.05 

0.1 

0.2 

0.3 

0.4  0.5  0.6  0.7 

0.8 
0.9 

1.0 

X1 

X2 

X4 

X6 

X8 

X10 

IDMT EARTH FAULT RELAY  

N202

a b c

d

e

f

f

g

h

a - Low-set start/trip status indicator
b - High-set start/trip status indicator
c - Auxiliary power supply indicator
d - Test button
e - Trip reset button
f - Earth-fault low-set adjustment
g - Delay time adjustment
h  - Earth-fault high-set adjustment

  IDMT Normal Inverse Curve 

Reviews: