8-14 Application BE1-CDS220
State Labels
Output
Purpose Description
Label
True False
VO4
Time overcurrent trip. May
be used to direct trip main
breaker or lockout.
OUT4 contact closes if any time
overcurrent (51N, 151P, N, or Q)
trip occurs.
151TRIP-OU
TRIP
NORMAL
BESTlogic Expression: VO4=51N+151PT+151NT+151QT
VO5
Time overcurrent trip. May
be used to direct trip main
breaker or lockout.
OUT5 contact closes if any time
overcurrent (251P, N, or Q) trip
occurs.
251 TRIP-OU
TRIP
NORMAL
BESTlogic Expression: VO5=251PT+251NT+251QT
VO6
Used to annunciate an
alarm.
OUT6 contact closes when any
programmed major alarm
condition is TRUE.
MAJOR-ALAR
ALARM
NORMAL
BESTlogic Expression: VO6=ALMMAJ
VO11 Protective trip expression.
VO11 is TRUE when any 87, 51,
151, or 251 element trips.
PROTECTIVE
TRIP
NORMAL
BESTlogic Expression: VO11=151PT+251PT+51NT+151NT+251NT+151QT+251QT+87RT+87UT
VO12
Protective pickup
expression.
VO12 is TRUE when any 87 or 51
element picks up.
PROT-PICKE
PU
NORMAL
BESTlogic Expression: VO11=87UT+51NPU+87RPU
(87UT is included to trigger the fault recorder because there is no unrestrained pickup output)
VO13
Optional. Use to annunciate
an alarm when alarm point
21 is enabled.
VO13 is TRUE when IN6 is TRUE.
IN6-ALARM
ACTIVE
NORMAL
BESTlogic Expression: VO13=IN6
VO14
Optional. Use to annunciate
an alarm when alarm point
22 is enabled.
VO14 is TRUE when IN7 is TRUE.
IN7-ALARM
ACTIVE
NORMAL
BESTlogic Expression: VO14=IN7
VO15
Optional. Use to annunciate
an alarm when alarm point
23 is enabled
VO15 is TRUE when IN8 is TRUE
IN8-ALARM
ACTIVE
NORMAL
BESTlogic Expression: VO15=IN8
BASIC TRANSFORMER WITH CONTROL LOGIC SCHEME
The Basic Transformer With Control Logic (TX-W-CTL) scheme was designed to provide a primary zone
of differential relaying and three backup zones of time overcurrent relaying for phase and ground faults in
two-winding transformer applications. This scheme also uses virtual control switch logic to eliminate the
need for external control switches.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......