13-40
Testing And Maintenance
BE1-CDS220
Table 13-25. Maximum Restraint Pickup Test Points (1 A Sensing Input)
Sensing
Input 1
Input 2
Increasing Input 1
Decreasing Input 2
Input Minimum slope
tap =
2.00
tap =
3.80
From Balance
From Balance
Type
Pickup
(%)
Bal. Input (A)
PU
Bal. Input (A)
PU
Pickup (A)
Pickup (A)
1
0.35
15
0.40 1 0.76 1
0.54
±
0.025 0.49
±
0.025
1
0.35
15
2.00 5 3.80 5
2.32
±
0.093 3.27
±
0.131
1
0.35
30
0.40 1 0.76 1
0.54
±
0.025 0.49
±
0.025
1
0.35
30
2.00 5 3.80 5
2.71
±
0.108 2.81
±
0.112
1
0.35
45
0.40 1 0.76 1
0.63
±
0.025 0.481
±
0.025
1
0.35
45
2.00 5 3.80 5
3.16
±
0.126 2.406
±
0.096
1
0.35
60
0.40 1 0.76 1
0.74
±
0.030 0.408
±
0.025
1
0.35
60
2.00 5 3.80 5
3.71
±
0.148 2.046
±
0.082
Step 14. Repeat for all values and optionally, reconnect to phases B and C, inputs 1 and 2 when
advancing through the set of test values in the table. It is not necessary to test each phase at
all the values listed to verify the response of each phase. If your relay is supplied with the HMI
option, navigate to the \PROT\SGn\87\87 screen to make the listed slope setting changes.
Notice that the test values in Tables 13-24 and 13-25 are intended to show operation on both the minimum
operate and slope portion of the operating curve. These tables have values for testing the relay either by
increasing one current from a balanced condition or decreasing it. Either technique can be utilized to test
this function. Refer to the descriptions of both methods to evaluate the differences in the two approaches.
Step 15. Verify that pickup occurred within the specified accuracy of the relay. Accuracy when
increasing or decreasing the input current is
±
4% of setting or 75 milliamperes (whichever is
larger) for 5 ampere sensing inputs and
±
4% of setting or 25 milliamperes (whichever is larger)
for 1 ampere sensing inputs.
Step 16.
Remove both currents.
Step 17. For each indicated change in slope value, send the commands listed in Table 13-26 to the
relay to invoke a change in slope settings (notice the leading comma (,) in the S#-87
command).
Table 13-26. Setup Commands
Command Purpose
A= Gain
access
S#-87=,30
Minpu = no change, slope = 30%
E Exit
Y Save
settings
Step 18. Repeat Steps 12, 13, and 14 for phases B and C unless all phases were tested during the
restraint testing in Steps 13 and 14. If so, proceed with the next step.
Step 19. (Optional) Repeat Steps 2 through 4 and 12 through 14 for setting groups 1 through 3 using
the CS/CO-GROUP command to change setting groups.
Restrained Time Verification
A timing circuit or a contact monitor with timing algorithm must be used to time the output contact status
change. For more information on determining the minimum pickup current, see Sidebar 13-8.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......