11-20 ASCII
Command
Interface BE1-CDS220
SL-43 Command
Purpose:
Read/Set Logic for Virtual switch (x43)
Syntax:
SL-{x}43[=mode] where x = blank/1/2/3/4/5/6/7, mode=0/1/2/3
Example:
SL-43 or SL-743=0 or SL-143=1
Reference: Section
4,
Protection and Control, Virtual Switches
SL-BF Command
Purpose:
Read/Set Logic for Breaker Failure Function Modules
Syntax:
SL-BF[{p}[={mode},{INI logic},{BLK logic}]]
Example:
SL-BF or SL-BF=1,VO1,0 or SL-BF=1,VO1,IN1
Reference: Section
4,
Protection and Control, BF Breaker Failure Protection
SL-50T Command
Purpose:
Read/Set Logic for x50 Function Modules where x = blank, 1 or 2
Syntax:
SL-x50T[{p}[={mode},{BLK logic}]] where p = P/N/Q and mode = 0/1/2
Example:
SL-50T or SL-50T=1,0 or SL-150TN=1,IN3 or SL-250TQ=2,IN2
Reference: Section
4,
Protection and Control, Overcurrent Protection
SL-51 Command
Purpose:
Read/Set Logic for x51 Function Modules where x = blank, 1 or 2
Syntax:
SL-x51[{p}[={mode},{BLK logic}]] where p = P/N/Q and mode = 0/1/2
Example:
SL-51 or SL-51P=1,0 or SL-151N=1,IN3 or SL-251Q=2,IN2
Reference: Section
4,
Protection and Control, Overcurrent Protection
SL-62 Command
Purpose:
Read/Set Logic for x62 Function Modules where x = blank or 1
Syntax:
SL-x62[={mode},{INI logic},{BLK logic}] where mode 1 - 6
Example:
SL-62 or SL-62=1,VO10,0 or SL-162=2,VO9,VO8
Reference: Section
4,
Protection and Control, General Purpose Logic Timers
SL-87 Command
Purpose:
Read/Set Logic for the 87 Function
Syntax:
SL-87[={mode},{BLK logic}]
Example:
SL-87 or SL-87=1,0 or SL-87=1,IN3
Reference: Section
4,
Protection and Control, Differential Protection
SL-87ND Command
Purpose:
Read/Set Logic for the 87ND Function
Syntax:
SL-87ND[={mode},{BLK logic}] where mode=0/1/2
Example:
SL-87ND or SL-87ND=1,0 or SL-87ND=2,IN3
Reference: Section
4,
Protection and Control, Differential Protection
User Programmable Name Setting Command
SN Command
Purpose:
Read/Set User Programmable Names
Syntax:
SN[-{var}[={name},{TRUE label},{FALSE label}]
Example:
SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED
Reference: Section
7,
BESTlogic Programmable Logic, User Input and Output Logic Variable Names
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......