TC-11

MULTIFUNCTIONAL TIME
RELAY (TIMER) 

1.0 version 

Summary of Contents for TC-11

Page 1: ...TC 11 MULTIFUNCTIONAL TIME RELAY TIMER 1 0 version ...

Page 2: ... conditions 5 60 C 0 85 RH non condensing Storage conditions 40 85 C 0 85 RH non condensing Power supply D1 triggering START STOP PAUSE commands D2 triggering RESET command Measuring time accuracy 0 1 Display and time unit setting method User selectable minutes seconds resolution 1 second hours minutes resolution 1 minute Work mode Time relay or time counter 6 user selectable operating modes with ...

Page 3: ...Using or set the minutes value and confirm with button Diodes go off start stop 4 2 TIME SETTING T2 only when the user chooses the operation mode with using two times T1 and T2 parameter F17 3 4 5 6 Hold button for 2 seconds Using or button Set the seconds value and confirm with key Then the minutes rate starts to flash Information To improve quick increasing or decreasing the settings values hold...

Page 4: ... Units Default Description F10 0 Unit and time range selection 0 minutes seconds range 00 01 99min 59s 1 hours minutes range 00 01 99h 59min F11 min s h min 01 00 Time setting T1 value Range 0 1 00 01 99 59 Group Operation parameters F12 min s h min 00 30 Time setting T2 value 00 01 99 59 1 F18 PAUSE function 0 inactive 1 active 0 1 F50 0 Digital input work mode see 6 2 F80 OFF Password to access ...

Page 5: ... the beeper Beeper operates for the time set in F83 parameter You can mute it with any button in any time czas T1 Output1 On Off Time Beeper On Off START Time czas T2 Time F83 F17 6 Delayed temporary switch on T2 Timer counts down T1 time after the START command After tha time timer turns on Output1 for T2 time and then the beeper Beeper operates for the time set in F83 parameter You can mute it w...

Page 6: ... With simple bipolar bistable or bell pulse monostable switch and choose one of the following digital input work modes in F50 parameter Shorting 4 5 contacts circuit the following commands will be triggered F50 1 START command only signal from bipolar or pulse switch Time Input D1 Closed Opened START Time Time count T1 8 0 1 2 3 4 5 6 7 T1 8 Time Input D1 Closed Opened Time Time count 0 1 2 3 4 5 ...

Page 7: ...ce 10 WIRING DIAGRAM Power supply D1 digital input START STOP PAUSE D2 digital input RESET OUT1 output 20A AC1 8A AC3 250V 6 3 EXTERNAL ALARM CONTROL RESET Reset command can be induced by a short circuit signal applied to D2 digital input The 2 3 contacts must be connected to the shorting pulse circuit element including the bell pulse switch monostable Short circuit of 2 3 contacts will induce RES...

Page 8: ...ters display Then release the buttons and the controller restores factory settings and goes into normal operation mode M set 8 Timer meets the requirements for immunity to electromagnetic interference in an industrial environment according to the following standards Electromagnetic compatibility EMC EN 61000 part 6 4 requirements for emissivity in an industrial environment EN 61000 part 6 2 requir...