BE1-CDS220 Protection
and
Control
4-37
BESTlogic Settings for General Purpose Logic Timers
BESTlogic settings are made from the
BESTlogic Function Element
screen in BESTCOMS. Figure 4-37
illustrates the BESTCOMS screen used to select BESTlogic settings for the
Logic Timer
elements. To
open the
BESTlogic Function Element
screen for
Logic Timer
, select
Logic Timers
from the
Screens
pull-
down menu. Alternately, settings may be made using the SL-x62 ASCII command.
Figure 4-37. BESTlogic Function Element Screen, 62
At the top center of the
BESTlogic Function Element
screen is a pull-down menu labeled
Logic
. This
menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. User or custom
logic must be selected on this menu in order to allow changes to the mode and inputs of the element.
Enable the
Logic Timer
function by selecting its mode of operation from the
Mode
pull-down menu.
To connect the element's inputs, select the button for the corresponding input in the
BESTlogic Function
Element
screen. The
BESTlogic Expression Builder
screen will open. Select the expression type to be
used. Then, select the BESTlogic variable, or series of variables to be connected to the input. Select
Save
when finished to return to the
BESTlogic Function Element
screen. For more details on the
BESTlogic Expression Builder
, see Section 7,
BESTlogic Programmable Logic
. Select
Done
when the
settings have been completely edited.
Table 4-19 summarizes the BESTlogic settings for General Purpose Logic Timers.
Table 4-19. BESTlogic Settings for General Purpose Logic Timers
Function Range/Purpose Default
Mode
0 = Disabled
1 = PU/DO
2 = One Shot Non-Retrig
3 = One Shot Retrig
4 = Oscillator
5 = Integrating
6 = Latch
0
INI
Logic expression that initiates timing sequence.
0
BLK
Logic expression that disables function when TRUE.
0
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......