6-22
Reporting and Alarm Functions
BE1-CDS220
Again, the setting is in terms of primary amps. The 0.5 power (i.e., square root factor) shown above for
the D
MAX
setting is to compensate for the fact that the relay internally squares the D
MAX
that is entered.
When testing the relay by injecting currents into the relay, the values in the duty registers should be read
and recorded prior to the start of testing. Once testing is complete and the relay is returned to service, the
registers should be reset to the original pre-test values. A block accumulation logic input may be used
when testing so that simulated breaker duty is not added to the duty registers. The BLKBKR logic function
is an OR logic term (e.g., IN1 or VO7) which blocks the breaker monitoring logic when TRUE (1).
BLKBKR is set to zero to disable blocking. When breaker monitoring is blocked (logic expression equals
1), breaker duty is not accumulated.
Protective
element
picks up
Protective
element
trips
Breaker auxiliary
contact changes
state
Protective
element
drops out
Fast
dropout
current
detector
drops out
SG-TRIGGER
-Pickup
-Logic
PU + logic
Fast dropout
current
detector
Breaker
status
Fault summary
report triggered
(When SG-TRIGGER (PU or Logic) is TRUE)
A
B
Targets logged
C
Fault clearing
time calculated
D
Breaker
operate time
Oscillographic
Record
pre-trigger
Post-trigger recording
Post-trigger
1/4 to 5 cycles
of pre-trigger
E
F
Fault currents
recorded
G
Red TRIP LED
flashing
(When SG-TRIGGER (PU) is TRUE)
H
Red TRIP LED
solid
Breaker interruption
duty
Transformer
fault duty
Setting group
change blocked
I
J
K
D2843-42
09-29-03
(SB-LOGIC setting)
-Trip
When
SG-TRIGGER
(PU or Logic)
goes FALSE
(When SG-TRIGGER (PU or Logic) is TRUE)
(When SG-TRIGGER (PU or Logic) is TRUE)
(When SG-TRIGGER (PU) is TRUE)
(When SG-TRIGGER (PU) is TRUE)
(When SG-TRIGGER (Trip) is TRUE)
Figure 6-9. Protective Fault Analysis
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......