8-8 Application
BE1-CDS220
Table 8-4. BASIC-87 Virtual Switch Logic
State Labels
Switch Purpose Mode
Label
Closed Open
N/A
No virtual switches used.
N/A
N/A
N/A
N/A
Table 8-5. BASIC-87 Output Logic
State Labels
Output Purpose
Description Label
True False
VOA
Relay Trouble alarm.
OUTA contact closes when
relay trouble alarm occurs.
RELAY-TROU ACTIVE
NORMAL
BESTlogic Expression: VOA=0
VO1
Phase differential trip. OUT1
is a high-speed trip contact.
OUT1 contact closes if
restrained or unrestrained trip
occurs.
87TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO1=87RT+87UT
VO2
Phase differential trip.
OUT2 contact closes if
restrained or unrestrained trip
occurs.
87TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO2=87RT+87UT
VO3
Phase differential trip.
OUT3 contact closes if
restrained or unrestrained trip
occurs.
87TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO3=87RT+87UT
VO4
Time overcurrent trip. May be
used to direct trip main
breaker or lockout.
OUT4 contact closes if any time
overcurrent (51P, N, or Q) trip
occurs.
51TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO4=51PT+51NT+51QT
VO6
Used to annunciate an alarm.
OUT6 contact closes when any
programmed major alarm
condition is TRUE.
MAJOR-ALAR ALARM
NORMAL
BESTlogic Expression: VO6=ALMMAJ
VO11
Protective trip expression.
VO11 is TRUE when any 87 or
51 element trips.
PROTECTIVE
TRIP
NORMAL
BESTlogic Expression: VO11=51PT+51NT+51QT+87RT+87UT
VO12
Protective pickup expression
VO12 is TRUE when any 87 or
51 element picks up
PROT-PICKE
PU
NORMAL
BESTlogic Expression: VO12=87UT+51PPU+51NPU+51QPU+87RPU (87UT is included to trigger the fault
recorder because there is no unrestrained pickup output)
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......