3-4
Input And Output Functions
BE1-CDS220
Sidebar 3-1. Determining the Transformer Connection Parameters
Wye and Autotransformer Windings. The transformer connection for a CT input circuit that is
connected to either a wye or autotransformer winding should be classified as a wye winding.
Delta Transformer Windings. The transformer connection for a CT input circuit that is connected to a
delta winding could be classified as one of two delta connections: Delta IA-IB (DAB), or Delta IA-IC
(DAC). A delta configuration is defined by the currents that flow in the primary phases connected to
the delta. The wye-winding phase connections are used as the point of reference since the current
that flows in the wye winding is the same as the current in the wye side primary phases. Figure 3-3
(left) shows an example of a transformer with a DAB connection. Figure 3-3 (right) shows an example
of the same transformer with the phases reconnected to provide a DAC connection. If there is no wye
winding to use as reference, as is the case with a delta/delta transformer, the definition of the delta
configuration is not important.
B
C
A
b
c
a
D2837-22.vsd
12-22-98
IA=Ia-Ic
IB=Ib-Ia
IA=Ic-Ib
B
A
C
b
a
c
D2837-21.vsd
12-21-98
IC=Ic-Ia
IB=Ib-Ic
IA=Ia-Ib
Figure 3-3. DAB Delta (left) and DAC Delta (right)
With the appropriate CT and transformer connection information, the relay can automatically determine
the correct compensation required. Table 3-2 provides a listing of all acceptable combinations of CT and
transformer connection settings and the compensation that the BE1-CDS220 will apply. The
recommended settings for each configuration are highlighted in Bold. Figure 3-3 provides details on how
to choose the correct CT and transformer connections to describe the application. If a combination of
connection settings is entered that results in an invalid condition, the relay will give an error message
when the settings are validated on Exit/Save Yes.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......