11-16 ASCII
Command
Interface BE1-CDS220
SA-BKR Command
Purpose:
Read/Set breaker alarm settings
Syntax:
SA-BKR[n][={mode},{alarm limit}] where mode=0-3(dis/%duty/#op/BkrOpTim)
Example:
SA-BKR or SA-BKR1=1,80 or SA-BKR2=2,250, or SA-BKR3=3,6c
Reference: Section
6,
Reporting and Alarm Functions, Breaker Monitoring
SA-DI Command
Purpose:
Read/Set demand alarm settings
Syntax:
SA-DI[p][={alarm level}] where p=P/N/Q, alarm level=Secondary Amps
Example:
SA-DI or SA-DIP=8.0 or SA-DIN=2.4
Reference: Section
6,
Reporting and Alarm Functions, Demand Functions
SA-DIFF Command
Purpose:
Read/Set differential alarm setting
Syntax:
SA-DIFF[={alarm level}] where alarm level=Percentage (0 (disable), 50 to 100)
Example:
SA-DIFF or SA-DIFF=75
Reference: Section
6,
Reporting and Alarm Functions, Differential Current Monitoring Function
SA-LGC Command
Purpose:
Read/Set logic alarm setting mask
Syntax:
SA-LGC[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-LGC or SA-LGC=2/6/7/10/11
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
SA-MAJ Command
Purpose:
Read/Set major alarm setting mask
Syntax:
SA-MAJ[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-MAJ or SA-MAJ=1/3/5/12
Reference: Section
6,
Reporting and Alarm Functions, Alarms Function
SA-MIN Command
Purpose:
Read/Set minor alarm setting mask
Syntax:
SA-MIN[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-MIN or SA-MIN=2/6/7/10/11
Reference: Section
6,
Reporting and Alarm Functions, Alarms Function
SA-RESET Command
Purpose:
Read/Set Programmable Alarms Reset logic
Syntax:
SA-RESET[={rst alm logic}]
Example:
SA-RESET or SA-RESET=VO1
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
SA-TX Command
Purpose:
Read/Set transformer alarm settings
Syntax:
SA-TX[n][={mode},{alarm limit}] where mode=0-2(disabled/%duty/#thflts)
Example:
SA-TX or SA-TX1=1,80 or SA-TX=2,250
Reference: Section
6,
Reporting and Alarm Functions, Transformer Monitoring
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......