BE1-CDS220 Protection
and
Control
4-33
Operating Settings for Breaker Failure
Operating settings are made using BESTCOMS. Figure 4-29 illustrates the BESTCOMS screen used to
select operational settings for the breaker failure element. To open
BESTlogic Function Element
screen
for the breaker failure element, select
Breaker Failure
from the
Screens
pull-down menu. Alternately,
settings may be made using the SP-BF ASCII command or through the optional HMI interface using the
\PROT\GLOBAL\BF Screen.
Figure 4-29. Breaker Failure Screen, 50BF Tab
Beside the
Logic
pull-down menu is a pull-down menu labeled
Settings
. The Settings menu is used to
select the setting group that the elements settings apply to.
The default unit of measure for the
Pickup
setting is secondary amps. The unit of measure for the
Time
setting that represents the element's time delay defaults to milliseconds. It is also selectable for seconds,
minutes, and cycles.
Table 4-18 summarizes the operating settings for Breaker Failure.
Table 4-18. Operating Settings for Breaker Failure
Setting Range
Increment
Unit of
Measure
Default
0 = Disabled
N/A
N/A
50 to 999 ms
1 m
Milliseconds
0.05 to 0.999 seconds
0.1 sec
Seconds
Timer Setting
0 to 59.94 (60 Hz) or 0 to 49.95 (50 Hz)
∗
Cycles
0
∗
Time delays less than 10 cycles can be entered to the nearest 0.1 cycles from the front panel HMI. All
time delays can be entered to the nearest 0.01 cycles from the ASCII command interface. Time delays
entered in cycles are converted to milliseconds or seconds. Increment precision after conversion is limited
to that appropriate for each of those units of measure.
Example 1.
Make the following operational settings to the breaker failure element. See Figure 4-51.
Timer Setting:
100
ms
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......