background image

Instruction Sheet

FuelMizer

SR501-OR-4 Switching Relay with Outdoor Reset

102-431

SUPERSEDES: March 1, 2013

EFFECTIVE: December 20, 2013

Plant ID# 9300-2871

ONE ZONE INSTALLATION W/O INDIRECT DHW

ONE ZONE

SWITCHING RELAY

WITH OUTDOOR RESET

S

R

 5

0

1

O

R

-4

LED

INDICATORS

POWER

TSTAT

DHW
OVERRIDE

BOILER
RELAY

N H

INPUT

120 VAC

ZONE 1

120 VAC

N H

6

AMP

X

R

BOILER

TSTAT

W C R

DHW

OUTDOOR

SENSOR

SUPPLY

SENSOR

X

DESIGN OUTDOOR

TEMPERATURE

FOR 180°F SUPPLY

TEMPERATURE

OFF

-30

-20

0

-10

10

20

40

30

ON

SW1

OFF

SYSTEM

CIRCULATOR

(OPTIONAL)

N

H

POWER

INPUT

(120 VAC)

24 VAC

THERMOSTAT

BOILER

CONTROL

OUTDOOR

SENSOR

BOILER

SUPPLY

SENSOR

POT1

See

 NOTE

NOTE:

 Resistor

(1K

Ω

1

2

 W)

may be needed
between 

W

 and 

C

terminals.

W

MULTI-ZONE INSTALLATION WITH ZONE CONTROL

AND WITH INDIRECT DHW

ONE ZONE

SWITCHING RELAY

WITH OUTDOOR RESET

S

R

 5

0

1

O

R

-4

LED

INDICATORS

POWER

TSTAT

DHW
OVERRIDE

BOILER
RELAY

N H

INPUT

120 VAC

ZONE 1

120 VAC

N H

6

AMP

X

R

BOILER

TSTAT

W

C R

W

DHW

OUTDOOR

SENSOR

SUPPLY

SENSOR

X

DESIGN OUTDOOR

TEMPERATURE

FOR 180°F SUPPLY

TEMPERATURE

OFF

-30

-20

0

-10

10

20

40

30

ON

SW1

OFF

SYSTEM

CIRCULATOR

(OPTIONAL)

N

H

POWER

INPUT

(120 VAC)

BOILER

CONTROL

OUTDOOR

SENSOR

BOILER

SUPPLY

SENSOR

POT1

1 2 3 4

ZONE 1

1 2 3 4

ZONE 2

1 2 3 4

ZONE 3

EXISTING

ZONE VALVE CONTROL

P

O

W

E

R

 I

N

2

4

 V

A

C

 

N/O COM N/C

PUMP END

SWITCH

FU

S

E

5

 A

M

P

ZONE 3 PUMP

END SWITCH

THERMOSTATS

(24VAC)

T STAT 1

VALVE 1

T STAT 2

VALVE 2

T STAT 3

VALVE 3

POWER

LED

INDICATORS

ZONE 1  ZONE 2  ZONE 3

ISOLATED

X

X

R W

R W

R W

END SWITCH

THERMOSTATS

PRIORITY

24 VAC ZONE VALVES

PRIORITY

X

X

ZONE 3

PRIORITY

OFF

ON

C

C

C

2 WIRE ZONE VALVE

(NO END SWITCH)
MUST USE JUMPER

TACO 3 WIRE
ZONE VALVE 

1
2
3

JUMPER

3 & 4

TACO 3 WIRE
ZONE VALVE 

1
2
3

DHW

AQUASTAT

A

CONTROL STRATEGY:

Outdoor Reset:

In order to properly control a hot water heating system, the heat sup-
plied to the building must equal the heat lost by the building. 

• The heat supplied to a building is proportional to the temperature of

the  supply  water  and  the  surface  area  of  the  heating  element.  A
small surface area such as baseboard radiators requires a higher
water temperature than a larger surface area such as radiant floors. 

• The heat lost from a building is dependent on the outdoor tem-

perature,  as  well  as  other  factors.  As  the  outdoor  temperature
drops, the building heat loss increases.

Reset Ratio:

Operation of a hot water heating system can generally be improved by
modulating the supply water temperature as the outdoor temperature
changes.  Using  this  approach,  the  heat  lost  from  the  building  is
matched by the heat input to the building. The SR501-OR boiler reset
control  utilizes  a  reset  ratio  to  set  the  relationship  between  outdoor
temperature and supply water temperature. The reset ratio determines
the amount the supply water temperature is raised for every 1° drop in
outdoor  air  temperature,  and  it  is  determined  from  the  starting  point
and the system design conditions. In order for the control to automat-
ically  determine  the  reset  ratio,  outdoor  design  conditions  must  be
established.  This is usually the typical coldest outdoor temperature
or  it  can  be  set  by  using  ASHARE  standards  for  Design  Outdoor
Temperature for specific geographic locations.

APPLICATION:

The SR501-OR is a microprocessor-based control designed to regulate
the  supply  water  temperature  of  a  single  boiler,  based  on  the  outdoor
temperature. The SR501-OR is a boiler reset control and switching relay
in one unit. The SR501-OR is ideal for retrofit application, but may also
be used in new installations as well.

The SR501-OR includes functions such as automatic reset ratio calcu-
lation, warm weather shut down (WWSD), minimum boiler temperature
setting, and boiler differential setting. The control also has boiler sensor
and outdoor sensor error checking.

40

30

20

10

0

-10

-20

-30

70

-20

90

130

110

150

170

180

190

210

90

80

70

60

50

40

30

20

10

0

-10

OUTDOOR TEMPERATURE (°F)

BOILER SUPPLY TEMPERATURE vs. OUTDOOR TEMPERATURE (°F)

FOR OUTDOOR DESIGN TEMPERATURES

B

O

IL

E

R

 S

U

P

P

LY

 T

E

M

P

E

R

A

T

U

R

E

 (

°F

)

For  information  on  Taco’s
Switching 

Relays 

(SR)

including  catalog  sheet,
instruction  sheets,  Visio
stencils  and  our  highly
praised 

Zone 

Controls

Wiring  Guide,  scan  the  QR
code  to  the  right  or  go  to
our website:

http://www.taco-hvac.com.

Summary of Contents for FuelMizer SR501-OR-4

Page 1: ...all surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor tem perature as well as other factors As the outdoor temperature drops the building heat loss increases Reset Ratio Operation of a hot water heating system can generally be improved by modulating the supply wate...

Page 2: ...r Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water ...

Page 3: ...gh limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent corrosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boil...

Page 4: ...64 9422 FAX 905 564 9436 Visit our web site at http www taco hvac com Printed in USA Copyright 2013 TACO Inc ond sensor can be placed alongside the one to be tested and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Usin...

Reviews: