background image

Boiler Operation:

The  supply  water  temperature  from  a  boiler  can  be  controlled  by
cycling  the  boiler  on  and  off.  Modulation  of  the  boiler’s  operating
temperature  in  hot  water  heating  systems  not  only  provides  more
comfort  but  also  offers  significant  energy  savings.  The  cooler  the
boiler runs, the more efficient it is due to less heat losses up the flue
and reduced boiler jacket losses. 

Differential:

An on / off boiler must be operated with a differential in order to pre-
vent short cycling. When the supply water temperature drops below
the bottom rail of the differential, the boiler is turned on. The boiler is
then kept on until the supply water temperature rises above the top
rail of the differential. If the differential is too wide, there can be large
supply  water  temperature  swings;  however,  if  the  differential  is  too
narrow, the boiler short cycles and operates inefficiently. This control
can  be  set  for  two  different  boiler  differentials,  10°F  (6°C)  or  20°F
(12°C).  This  setting  will  help  to  achieve  an  appropriate  balance
between temperature swings and boiler efficiency. 

Minimum Boiler Supply:

Most boilers require a minimum supply water temperature in order to
prevent  corrosion  from  flue  gas  condensation.  The  control  should
therefore only modulate the boiler supply water temperature down to
the boiler manufacturer’s minimum recommended operating temper-
ature. Some boilers are designed to condense and should be oper-
ated  at  low  water  temperatures  as  much  as  possible  for  maximum
efficiency.

S

U

P

P

L

Y

 W

A

T

E

R

 T

E

M

P

E

R

A

T

U

R

E

TIME

Differential = 10

°F (5 °C)

165

°F(74 °C)

155°F (68 °C)

160°F (7 1°C)

BOILER ON

BOILER ON

BOILER OFF

BOILER OFF

OUTDOOR AIR TEMPERATURE

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

90

(32)

WWSD

TEMPERATURE

°

F (

°

C)

SU

PP

LY

 W

AT

ER

 T

EM

PE

RA

TU

RE

110 (43)

70 (21)

90 (32)

210 (99)

170 (77)

150 (65)

130 (54)

190 (88)

RESET

RATIO

BOILER

MINIMUM

SEQUENCE OF OPERATION:

Powering Up the Control:

After the SR501-OR is powered up, the green power LED light will be on.

Heating Demand:

The SR501-OR receives a heating demand from thermostat or zone
control end switch closure on the R and W thermostat terminals. The
thermostat red LED light will also be turned on. The control can be
setup for boiler temperature reset or ON – OFF boiler operation.

Reset Demand:

When the SR501-OR receives a heating demand the controls enable
the  boiler  based  on  the  reset  curve.  The  Boiler  Relay  red  LED  light
will be turned on when the boiler relay is energized.

DHW Demand:

When  the  SR501-OR  receives  a  DHW  demand  the  controls  enable
the boiler and ignore the boiler reset curve.  The DHW Override red
LED light will also be turned on.

Warm Weather Shut Down (WWSD):

When the outdoor temperature rises above 70°F (21°C), the control
turns off the boiler and blinks the Thermostat LED light. This function
only applies for space heating and does not affect DHW operation.

Boiler Operation:

When the SR501-OR has a reset demand, the system supply water
temperature is controlled by turning the boiler on and off. The control
calculates the target supply water temperature based on the outdoor
temperature, and the settings that were entered. The boiler operates
around a differential that is manually set by dip switch number 2. The
control includes a minimum on and off time for the boiler, in order to
minimize short cycling. 

Maximum Boiler Supply: 

The  SR501-OR  does  not  allow  the  boiler  target  temperature  to
exceed the boiler design temperature setting plus 10°F (6°C) up to a
maximum of 225°F (107°C). 

Minimum Boiler Supply: 

The SR501-OR has a 140°F minimum boiler setting which is used in
order  to  prevent  corrosion  from  flue  gas  condensation.  During  mild
outdoor conditions, the boiler cycles around the minimum boiler set-
ting.  This  programmed  function  can  be  set  to  the  OFF  setting  for
condensing and electric boilers.

INSTALLATION:

Step One:

Check the contents of this package. If any of the contents listed are
missing  or  damaged,  please  contact  your  sales  representative  for
assistance. The SR501-OR includes:

SR501-OR Boiler Reset Control and Switching Relay Combination
One Outdoor Sensor
One Strap on Sensor
Instruction Sheet 

Replacement sensors are available from Taco, Inc.:

Strap on Sensor – 9300-2044RP
Outdoor Sensor – 9300-2052RP 

Note:

Carefully read the details of the Sequence of Operation section

in this brochure to ensure that you have chosen the proper control for
your application. 

Step Two:

Installing the Control:

The  enclosure  is  to  be  mounted  flush  onto  a  wall  or  any  ridge  sur-
face.

• The mounting holes in the enclosure accept #6 screws. 
• Line voltage to enter from bottom of control and low voltage to

enter from top of control.

Installing the Outdoor Sensor:

Note:

The temperature sensor (thermistor) is built into the enclosure.

• Use one round or pan head screw to attach the base of the sen-

sor to the wall.

• The  sensor  is  wall  mounted  and  the  wiring  enters  through  the

bottom of the enclosure. The hole for the cable entry must face
downward in order to prevent water from entering and filling the
enclosure.

CAUTION: Improper installation and operation of this control
could  result  in  damage  to  the  equipment  and  possibly  even
personal injury. It is your responsibility to ensure that this con-
trol  is  safely  installed  according  to  all  applicable  codes  and
standards. This electronic control is not intended for use as a
primary limit control. Other controls that are intended and cer-
tified as safety limits must be part of the control circuit. 

Summary of Contents for FuelMizer SR501-OR-4

Page 1: ...all surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor tem perature as well as other factors As the outdoor temperature drops the building heat loss increases Reset Ratio Operation of a hot water heating system can generally be improved by modulating the supply wate...

Page 2: ...r Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water ...

Page 3: ...gh limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent corrosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boil...

Page 4: ...64 9422 FAX 905 564 9436 Visit our web site at http www taco hvac com Printed in USA Copyright 2013 TACO Inc ond sensor can be placed alongside the one to be tested and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Usin...

Reviews: