BE1-CDS220
Time Overcurrent Characteristic Curves
A-1
APPENDIX A • TIME OVERCURRENT
CHARACTERISTIC CURVES
GENERAL
Basler Electric inverse time overcurrent systems (ANSI Device 51) provide time/current characteristic
curves that very closely emulate most of the common electro-mechanical, induction disk relays that were
manufactured in North America. To further improve proper relay coordination, selection of integrated reset
or instantaneous reset characteristics is also provided.
CURVE SPECIFICATIONS
Timing Accuracy (All 51 Functions):
Within ±5% or ±1½ cycles, whichever is greater,
for time dial settings of D greater than 0.1 and
multiples of 2 to 40 times the pickup setting but
not over 150 A for 5 A CT units or 30 A for 1 A CT
units.
Sixteen
inverse
time
functions,
one
fixed
time
function, and one programmable time function can
be selected. Characteristic curves for the inverse
and definite time functions are defined by the
following equations and comply with IEEE
C37.112 - 1996.
K
D
B
C
M
D
A
T
N
T
+
⋅
+
−
⋅
=
Equation A-1
1
M
D
R
T
2
R
−
⋅
=
Equation A-2
T
T
= Time to trip when M
≥
1
T
R
= Time to reset if relay is set for integrating
reset when M
<
1. Otherwise, reset is 50
milliseconds or less
D
= TIME DIAL setting (0.0 to 9.9)
M
= Multiple of PICKUP setting (0 to 40)
A, B, C, N, K
= Constants for the particular curve
R
= Constant defining the reset time.
Table A-1 lists time characteristic curve constants.
See Figures A-1 through A-16 for graphs of the
characteristics.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......