Technical Data
Designation
7UG0 480-1IU20
Type
Temperature controller relay
Control voltage
85 - 270V AC/DC (±15%) , 50/60Hz
Operating conditions
0 to 50°C ,
upto 95%RH (non-condensing)
Input Sensors
Thermocouple (J,K,T,R,S) /
RTD (PT100)
Filter time
0.2 to 10 sec
Digital output for external SSR
12VDC, 50mA
Accuracy
For J,K,T inputs: ±(2% of s 1°)
For R,S inputs: ±(2% of s 2°)
For RTD inputs: ±(2% of s 1°)
(20 min of warm up time for TC inputs)
Control action
1. PID control with auto or self tuning
2. ON - OFF control
3. Heat - Cool with auto tuning
Propostional band (P)
0°C to 400°C / 1.0°F to 750°F
Integral time (I)
0 to 9999 sec
Derivative time (D)
0 to 9999 sec
Cyclic time
0 to 99.9 sec
Hysteresis width
0.1 to 99.9°
Dwell timer
0 to 9999 min
Manual reset value
-19.9 to 19.9°
Heat Cool PID
Control Method: PID
Proportional band - Cool: 0 to 400°C
Cyclic time - Cool: 0.1 to 99.9sec
Dead band: Programmable from
setpoint low limit to setpoint high limit
Power consumption @ 230V AC
6VA
Rated current of relay output
(@250VAC)
5A (AC12), 2A (AC15)
SCPD for relay output (For
Short circuit current of 1kA as
per IEC 60947-5-1)
6A, gL, HRC fuse
Terminal connections
7UG048...
0.5 Nm
Solid
1 x (0.75 to 2.5) mm
2
2 x 0.5 to 2 x 1.5 mm
2
Stranded with end sleeve
1 x (0.5 to 2.5) mm
2
2 x (0.5 to 1.5) mm
2
N
L
C
NO
TC
LOAD
R
C
TC
Snubber
MOV
TC
TC
N
L
Snubber
C
NO
R
C
Contactor
LOAD
C
MOV
For bigger loads, use interposing relay / contactor
For load current less than 0.5A