BE1-CDS220 Application
8-19
Function
Purpose
BESTlogic
Expression
Mode Setting
151Q
Used for timed negative sequence-overcurrent protection for CT input
circuit 1.
0
1 (CT Input 1)
GROUP
Auto/Manual Logic: Disable automatic selection when virtual switch
343 is in the manual position.
/343
1 (Discrete
Inputs)
251P
Used for timed phase-overcurrent protection for CT input circuit 2.
0
2 (CT Input 2)
251N
Used for timed neutral-overcurrent protection for CT input circuit 2.
0
2 (CT Input 2)
251Q
Used for timed negative sequence-overcurrent protection for CT input
circuit 2.
0
2 (CT Input 2)
Table 8-14. TX-W-CTL Virtual Switch Logic
State Labels
Switch Purpose
Mode
Label
Closed Open
43
Trip high-side breaker (1).
3 (OFF MOM-ON)
BREAKER1-T
TRIP
NORMAL
143
Close low-side breaker (1).
3 (OFF MOM-ON)
BREAKER1-C
CLOSE
NORMAL
243
Differential Cutoff switch. The 87
function is blocked when the switch is
closed.
2 (ON/OFF)
87-CUTOFF
DISABLD
NORMAL
343
Automatic setting group change logic
auto/manual switch.
2 (ON/OFF)
SETGRP-CON MANUAL
AUTO
101
Allows breaker to be tripped or closed
manually from HMI or ASCII command
interface.
1 (ENABLED)
N/A
N/A
N/A
Table 8-15. TX-W-CTL Output Logic
State Labels
Output
Purpose Description
Label
True False
VOA
Relay Trouble alarm.
OUTA contact closes when relay
trouble alarm occurs.
RELAY-TROU
ACTIVE
NORMAL
BESTlogic Expression: VOA=0
VO1
Phase differential trip.
OUT1 is a high-speed trip
contact.
OUT1 contact closes if a
restrained, unrestrained, or time
overcurrent trip occurs.
TRIP_86T-O
TRIP
NORMAL
BESTlogic Expression: VO1=87RT+87UT+51NT+151PT+151NT+151QT
VO2
Breaker 1 Trip.
OUT2 contact closes if restrained
or unrestrained trip occurs or for
51 or 151 trip or for control switch
trip.
TRIP-BKR1-
TRIP
NORMAL
BESTlogic Expression: VO2=87RT+87UT+51NT+151PT+151NT+151QT+43
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......