BE1-CDS220 Application
8-47
Table 8-28. MOTOR Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode Setting
87
Used for percent-restrained differential protection with high-speed
unrestrained instantaneous differential protection.
43
1 (Enabled)
51P
51P is used for motor overload protection. Blocking during starting is
not required since this element is slower than the LR protection. It
serves as backup during starting.
0
1 (CT Input 1)
51Q
51Q is used for unbalance protection (46).
0
1 (CT Input 1)
151P
The 151P element provides locked rotor protection for high inertia
motors. Blocked when low inertia is selected by switch 243. If high
Inertia is selected, it is unblocked when starting as determined by
intermediate logic VO7.
/VO7+/243
1 (CT Input 1)
251P
This element protects for a jam condition. It is blocked while the
motor is starting as determined by VO8.
VO8
1 (CT Input 1)
50TP
50TP is used for motor start detection (50S). Target should not be
enabled with the SG-TARG setting for this function.
0
1 (CT Input 1)
50TN
50TN is used for ground fault backup protection.
0
1 (CT Input 1)
50TQ
50TQ is used for loss of phase detection.
0
1 (CT Input 1)
150TP
This element provides LR protection for low inertia motors. It is
blocked when the motor is running (after the 250TP time setting
expires) or when the high inertia mode is selected.
243+250TPT
1 (CT Input 1)
250TP
The 250TP is used to detect when the motor is running. It supervises
the 150TP locked rotor protection for low inertia motor applications
and the 251P jam protection. Target should not be enabled with the
SG-TARG setting for this function.
0
1 (CT Input 1)
Table 8-29. MOTOR Virtual Switch Logic
State Labels
Switch
Purpose Mode
Label
Closed Open
143
Speed Switch selector. When enabled, the motor
starting is determined by speed switch. When
None, starting is determined by current detector
set at 85% of locked rotor current.
2 (On/Off)
SPEED-
SWIT
ENABLED
NONE
243
Selector switch to customize the protection for
high or low inertia applications. When high is
selected, blocks 150TP and enables 151P for
locked rotor protection.
2 (On/Off)
INERTIA-MO
HIGH
LOW
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......