BE1-CDS220
Testing And Maintenance
13-67
Command
Purpose
S0-62=15s,5s
Sets T1 at 15 seconds, T2 at 5 seconds
EXIT
Exit
Y Save
settings
Step 2.
Send the commands in Table 13-77 to the relay. These commands supply a block input to the
62 timer by changing the 43 switch state to TRUE.
NOTE
The CS and CO commands of Table 13-77 are performed three times. Follow the timing
sequence to illustrate timer mode action. The time delay settings may be increased if
difficulty is encountered with repeating the 43 switch actions.
Table 13-77. x62 Mode 5 Timer Initiate Commands
Command
Purpose
A=
Gain write access
CS-43=1
Selects 43 for TRUE operation
CO-43=1
Executes 43 for TRUE operation
Wait no longer than 10 seconds to interrupt the T1 timer
CS-43=0
Selects 43 for FALSE operation
CO-43=0
Executes 43 for FALSE operation
Wait at least 5 seconds for the T2 timer to time out and reset the integration
CS-43=1
Selects 43 for TRUE operation
CO-43=1
Executes 43 for TRUE operation
Wait at least 20 seconds for the T1 timer to elapse
E
Exit
Step 3.
Use the RS-LGC command to obtain an SER report and verify that the following actions were
logged. These events are illustrated in the timing diagram of Figure 13-20.
Timer T1 failed to time out in the first 43 switch action (TRUE).
Timer T2 timed out after the second 43 switch action (FALSE).
Timer T1 timed out and the 62 timer output went TRUE.
Timer T2 timed out and the 62 timer output returned to a FALSE state
15 s
5 s
>5 s
43
BLK
Timer
x62
1
1
1
100%
0
0
0
0%
D2595-05.cdr
07-19-00
Figure 13-20. x62 Mode 5 (Integrating) Timing Example
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......