4-38 Protection
and
Control BE1-CDS220
Example 1.
Make the following settings to the 62 Logic Timer. Figure 4-37 illustrates these settings.
Logic:
User
Mode:
One Shot Non-Retriggerable
INITIATE:
IN2
BLOCK:
0
Operating Settings for General Purpose Logic Timers
Operating settings are made using BESTCOMS. Figure 4-38 illustrates the BESTCOMS screen used to
select operational settings for the Logic Timer elements. To open the
Logic Timers
screen, select
Logic
Timers
from the
Screens
pull-down menu. Alternately, settings may be made using the S<g>-x62 ASCII
command or through the optional HMI interface using Screen 5.#.5.1, \PROT\SG#\62\SETTINGS.
Figure 4-38. Logic Timers Screen
At the top left of the screen is a pull-down menu labeled
Logic
. This menu allows viewing of the
BESTlogic settings for each preprogrammed logic scheme. User or custom logic
must
be selected on this
menu in order to allow changes to be made to the mode and inputs of the element.
Beneath the
Logic
pull-down menu is a pull-down menu labeled
Settings
. The Settings menu is used to
select the setting group that the element's settings apply to. See Section 7,
BESTlogic Programmable
Logic, Logic Schemes
.
Using the pull-down menus and buttons, make the application appropriate settings to the Logic Timer
elements.
Table 4-20 summarizes the operating settings for General Purpose Logic Timers.
Table 4-20. Operating Settings for General Purpose Logic Timers
Setting
Range
Increment
Unit of Measure
Default
0 to 999 ms
1
Milliseconds
0.1 for 0.1 to 9.9 sec.
0.1 to 9999 sec.
1.0 for 10 to 9999 sec.
Seconds
T1 Time,
T2 Time
0 to 599,940 (60 Hz)
0 to 499,950 (50Hz)
∗
Cycles
0
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......