BE1-CDS220 Application
8-13
Table 8-8. BASIC-TX Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode Setting
87
Used for percent-restrained differential protection with high-speed
unrestrained instantaneous differential protection.
0
1 (Enabled)
51N
Used for timed ground-overcurrent protection for independent
ground input circuit.
0
G (Ground Input)
151P
Used for timed phase-overcurrent protection for CT input circuit 1.
0
1 (CT Input 1)
151N
Used for timed neutral-overcurrent protection for CT input circuit 1.
0
1 (CT Input 1)
151Q
Used for timed negative sequence-overcurrent protection for CT
input circuit 1.
0
1 (CT Input 1)
GROUP
Auto/Manual Logic: Set to 1 (/0) to enable automatic selection. No
manual selection is used.
/0
1 (Discrete
Inputs)
251P
Used for timed phase-overcurrent protection for CT input circuit 2.
0
2 (CT Input 2)
251N
Used for timed neutral-overcurrent protection for CT input circuit 2.
0
2 (CT Input 2)
251Q
Used for timed negative sequence-overcurrent protection for CT
input circuit 2.
0
2 (CT Input 2)
Table 8-9. BASIC-TX Virtual Switch Logic
State Labels
Switch Purpose Mode
Label
Closed Open
N/A
No virtual switches used.
N/A
N/A
N/A
N/A
Table 8-10. BASIC-TX Output Logic
State Labels
Output
Purpose Description
Label
True False
VOA
Relay Trouble alarm.
OUTA contact closes when relay
trouble alarm occurs.
RELAY-TROU
ACTIVE
NORMAL
BESTlogic Expression: VOA=0
VO1
Phase differential trip. OUT1
is a high-speed trip contact.
OUT1 contact closes if restrained
or unrestrained trip occurs.
87TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO1=87RT+87UT
VO2
Phase differential trip.
OUT2 contact closes if restrained
or unrestrained trip occurs.
87TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO2=87RT+87UT
VO3
Phase differential trip.
OUT3 contact closes if restrained
or unrestrained trip occurs.
87TRIP-OUT
TRIP
NORMAL
BESTlogic Expression: VO3=87RT+87UT
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......