Technical data
.................................................................................................................................................................................................................................
Rack dimensions
The racks require an area of 600 mm [23.622”] x 600 mm [23.622”] (width x depth).
This area represents the absolute system limits which must not be exceeded in the
operating state by protruding elements such as switches or plugs. The standard height
is 2200 mm [86.614”] for an ETSI-2 rack and 2125 mm [83.661”] for a NEBS-2000
rack. The racks are designed to accommodate two
LambdaUnite
®
MSS subracks.
Rack weights
The ETSI-2 rack has a maximum weight of 92.3 kg [203.5 lbs] (including PDP, rack
cables and 2 door sets).
The NEBS-2000 rack has a maximum weight of 90.5 kg [199.6 lbs] (including PDP,
rack cables and 2 door sets).
Subrack weight
The subracks have a maximum weight of 51 kg [112.46 lbs] (including user panel, fan,
PIs, CI-CTL, TIs and 12x blanks at the rear).
Power consumption
The power consumption of
LambdaUnite
®
MSS depends on its configuration
(160-Gbit/s, 320-Gbit/s, or 640-Gbit/s configuration) and on its equipage.
The maximum power consumption is as follows:
•
1845 W for the 160-Gbit/s configuration
•
3290 W for the 320-Gbit/s configuration
•
3500 W for the 640-Gbit/s configuration.
General information
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
2-5