Proceed as follows to check the “Minor” alarm reporting:
.................................................................................................................................................................................................
1
Remove the “POWER INPUT A” cable from the fan unit. You can do this without
switching off the power supply.
.................................................................................................................................................................................................
2
In the
WaveStar
®
CIT
System View
, select
Fault
→
NE Alarm List...
or
Reports
→
NE Alarm List...
to check if the “Fan Voltage Feed A Failure” alarm is reported to the
WaveStar
®
CIT. Check also the correct behavior on the User Panel (“MN” LED is
illuminated) and on the rack alarm lamps (“Minor” LEDs are illuminated).
.................................................................................................................................................................................................
3
Reconnect the “POWER INPUT A” cable. You can do this without switching off the
power supply.
.................................................................................................................................................................................................
4
Check the
WaveStar
®
CIT alarm list for correct clearing of the reported alarm. To
make sure that the “NE Alarm List” reflects the current alarm status, click the
Refresh
button. Furthermore, the “MN” LED on the User Panel and the “Minor” LED at the
rack top should be extinguished.
Critical alarm test
Proceed as follows to check the “Critical” alarm reporting:
.................................................................................................................................................................................................
1
In the
WaveStar
®
CIT
System View
, click one optical port (without fiber connection)
with the
right
mouse button and select
Provision Port # ...
.
Stand-alone test procedures
Alarm reporting tests
.................................................................................................................................................................................................................................
8-4