CAUTION: This equipment is designed to permit the connection of the grounded
conductor of the DC supply circuit to the grounding conductor at the equipment.
1. This equipment shall be connected directly to the DC supply system grounding
electrode conductor or to a bonding jumper from a grounding terminal bar or
bus to which the DC supply system grounding electrode conductor is connected.
2. This equipment shall be located in the same immediate area (such as, adjacent
cabinets) as any other equipment that has a connection between the grounded
conductor of the same DC supply circuit and the grounding conductor, and also
the point of grounding of the DC system. The DC system shall not be grounded
elsewhere.
3. The DC supply source is to be located within the same premises as this
equipment.
4. There shall be no switching or disconnection devices in the grounded circuit
conductor between the DC source and the point of connection of the grounding
electrode conductor.
CAUTION
Laser hazard
LambdaUnite
®
MSS systems contain optical circuit packs that can emit laser radiation
assessed as IEC Hazard Level 3A or IEC Hazard Level 1M.
Therefore,
LambdaUnite
®
MSS systems may only be installed in restricted access
locations! Restricted access locations are controlled environments where there is no
ready access to the general public, but only to authorized persons who have received
adequate training in laser safety.
Safety
Basic safety aspects
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
1-9