Floorplan guidelines (ETSI-2 / NEBS-2000)
.................................................................................................................................................................................................................................
Overview
This section describes the floorplan data for both rack types (ETSI-2 and NEBS-2000).
NOTE:
For exact measurements see the relevant project documents. Local
circumstances can allow deviations from these guidelines.
Guidelines
Use the following figures and data as guidelines:
•
a = >1200 mm [47.244”]
•
b = >1800 mm [70.866”]
•
c = >3400 mm [133.858”]
•
d = n x 600 mm [23.622”] (n = number of cabinets) or
d = n x 750 mm [29.527”] (n = number of cabinets with rack extension)
Figure 2-1 Floorplan guidelines (top view)