Mounting the airguide
.................................................................................................................................................................................................................................
Before you begin
The airguide (CC848920534) described below prevents air flow from the MADM
subrack into the
LambdaUnite
®
MSS subrack. It is part of the mixed configuration kit
(CC848914271).
Procedure
Proceed as follows to mount the airguide:
.................................................................................................................................................................................................
1
Mount one airguide directly above each mounted MADM subrack using two M6x16
hexagon bolts (CC847079860) as shown in the figure below. Use the hole position #43
(see
Figure D-10, “Mounting positions (
Result
Figure D-5 Airguide mounting
Mixed configuration:
LambdaUnite
®
MSS and
Metropolis
®
ADM
.................................................................................................................................................................................................................................