2
Set the
Port Mode
to
Monitored
.
.................................................................................................................................................................................................
3
Click
OK
and then
Yes
in the confirmation window.
.................................................................................................................................................................................................
4
Select
Fault
→
NE Alarm List...
or
Reports
→
NE Alarm List...
to check if the “Loss
of Signal” alarm is reported for that port to the
WaveStar
®
CIT. Check also the correct
behavior on the User Panel (“CR” and “NE ACTY” LEDs are illuminated), on the rack
alarm lamps (“Critical” LEDs are illuminated) and on the circuit pack (“Fault” LED
flashes).
.................................................................................................................................................................................................
5
Right click the same optical port as done in
, and select
Provision Port # ...
.
.................................................................................................................................................................................................
6
Set the
Port Mode
to
Auto
.
.................................................................................................................................................................................................
7
Click
OK
and then
Yes
in the confirmation window.
.................................................................................................................................................................................................
8
Check the
WaveStar
®
CIT alarm list for correct clearing of the reported alarm. To
make sure that the “NE Alarm List” reflects the current alarm status, click the
Refresh
button. Furthermore, the “CR” and “NE ACTY” LEDs on the User Panel, the
“Critical” LEDs at the rack top and the “Fault” LED on the circuit pack should be
extinguished.
Major alarm test
CAUTION
ESD hazard
Electronic components can be destroyed by electrostatic discharge.
Always observe the ESD instructions (cf.
“Electrostatic discharge” (p. 1-20)
Stand-alone test procedures
Alarm reporting tests
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
8-5