Rack extension (height)
.................................................................................................................................................................................................................................
Purpose
This rack extension is used to enlarge the rack frame with a height of 400 mm
[15.748”]. The additional space can be used for STM-1e cable excess lengths, for
example.
Available rack extensions
The following rack extensions are available:
•
Rack extension (height), 600 mm [23.622”] x 400 mm [15.748”] — CC848902656
This rack extension must be used for racks without rack extensions (width).
•
Rack extension (height), 750 mm [29.527”] x 400 mm [15.748”] — CC848902664
This rack extension must be used for racks with rack extensions (width).
Mounting
Proceed as follows to mount the rack extension:
.................................................................................................................................................................................................
1
Mount the two extension plates (SC1000501, item 3) to the top of the rack frame with
the help of four screws (Hexagonal bolt, STL ST-70, M12x20 — CC847191574) as
shown in the figure below.
.................................................................................................................................................................................................
2
Mount the bracket for coverplate left (CC848301925, item 1) to the left extension plate
and the bracket for coverplate right (CC848301933, item 2) to the right extension
plate.
.................................................................................................................................................................................................
3
Mount the coupling brackets (SC1000504, item 4), which connect the side plates of the
rack extension, on both sides (front and rear).
.................................................................................................................................................................................................
4
Click the coverplate (CC848302543, item 5) on the bracket, when all cables are routed
to the subrack(s).
Mechanical installation
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
3-17