Mounting the anti-recirculation plate
.................................................................................................................................................................................................................................
Purpose
The anti-recirculation plate is necessary to prevent heat air circulation within the rack.
Mounting
Proceed as follows to mount the anti-recirculation plate:
.................................................................................................................................................................................................
1
Place the anti-recirculation plate (DC1006435, item 1) at the rack rear side between the
rack bottom and the
LambdaUnite
®
MSS subrack.
Important!
The top of the anti-recirculation plate must partly be placed into the
airinlet of the
LambdaUnite
®
MSS subrack.
.................................................................................................................................................................................................
2
Mount the anti-recirculation plate at hole positions #69 and #77 (see section
) using M6x16 screws (CC901331421) as shown in the figure below.
Mixed configuration:
LambdaUnite
®
MSS and
Metropolis
®
DMX (High Capacity)
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
E-7