Cable connection
.................................................................................................................................................................................................
1
Remove the protection cap by unscrewing the two screws at the bottom of the
protection cap.
.................................................................................................................................................................................................
2
Remove the strain relief by unscrewing the four screws.
.................................................................................................................................................................................................
3
Connect the pre-mounted rack cables of the rack frame to the studs of the PI/100 unit
with 16.5 Nm (12 ft. lbs.) torque.
Important!
For subrack installation in North America without the rack frame,
customer-provided input power cables must be assembled with
UL Listed copper
compression type terminals
and must be fastened via nuts and washers to the
PI/100 studs with
16.5 Nm (12 ft. lbs.) torque
.
.................................................................................................................................................................................................
4
Mount the strain relief. Secure the four screws with a torque of 1 Nm starting with the
two middle screws.
Important!
Spare screws are available from the other unused strain relief.
.................................................................................................................................................................................................
5
Mount the protection cap back in position.