10.
Primary Slide Position Sensor
This drop down list is used to select the type of sensor that monitors the current position of the capacity
slide valve. The options are dependent on the brand and series of the compressor.
11.
Process Temperature
This drop down list is used to select where the compressor is equipped with process temperature sen-
sors. The options are:
•
None
•
Inlet Temperature
•
Outlet Temperature
•
Both
12.
Pump Down
This drop down list is used to select when the compressor will enter
Pump Down
mode. In
Pump Down
mode the compressor will be used to evacuate refrigerant from a chiller. The options are:
•
Disabled
•
Manual
•
Auto
13.
Suction Filter Combo Solenoid
This drop down list is used to enable control of the suction filter combo solenoid. Most GEA compressors
will use this control. The options are:
•
None
•
Normally Open
•
Normally Closed
14.
Double Balance Piston Pressure Transducer
This drop down list is used to select the range of the pressure transducer associated with the double
balance piston.
15.
Remote Start Stop
This check box is used to select if the panel is equipped with an input to remotely start or stop the com-
pressor.
16.
Remote Control I/O
This check box is used to select if the panel is equipped with digital modules for remote control of the
compressor.
17.
VTrac
This check box is used to select whether the package is equipped with a VTrac Vibration monitor.
Instruction Manual | GEA Omni™
Control panel
Control
Configuration
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
189