Parameter
Units
Minimum
Maximum
Default
Low Motor Current Shutdown
Amps
0 A
235 A
10 A
Low Motor Current Shutdown Timer
Seconds
0 s
30 s
8 s
Limitation Motor Current Load
Inhibit Offset
Amps
0 A
300 A
15 A
Limitation Motor Current Force
Unload Offset
Amps
0 A
300 A
10 A
1.
Motor Current Nominal FLA
This parameter is used to select the
Full Load Amps
(FLA) value of the motor. This value may be found on
the nameplate of the motor. The value is measured in amps.
2.
High Motor Current Shutdown Run Delay
This parameter is used to select a period of time after the compressor is started during which the high motor
current safeties will be ignored. The value is measured in seconds.
3.
High Motor Current Shutdown
This parameter is used to select the motor current above which a
High Motor Current Shutdown
will be
annunciated. The value is measured in amps.
4.
High Motor Current Shutdown Timer
This parameter is used to select the amount of time that the motor current must exceed the
High Motor Cur-
rent Shutdown
value before a
High Motor Current Shutdown
will be annunciated. The value is measured in
seconds.
5.
High Motor Current Warning Offset
This parameter is used to set an offset value subtracted from the value of the
High Motor Current Shutdown
parameter. If the motor current exceeds this calculated value, a
High Motor Current Warning
will be annunci-
ated. The value is measured in amps.
6.
Illegal Compressor Motor Current Shutdown
This parameter is used to select the maximum percentage of the FLA that motor current may reach while the
motor starter is not energized. If this value is exceeded while the motor starter is still de-energized, an
Illegal
Compressor Motor Current Shutdown
will be annunciated. The value is measured in percent.
7.
Low Motor Current Run Delay
This parameter is used to select a period of time after the compressor is started during which the low motor
current safeties will be ignored. The value is measured in seconds.
8.
Low Motor Current Shutdown
This parameter is used to select the set point for the
Low Motor Current Shutdown
. If the motor current falls
below this value for a user defined period of time, a
Low Motor Current Shutdown
will be annunciated. The
value is measured in amps.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016