Oil Pump Drain Timer
This parameter is used to select the amount of time the compressor must wait whenever oil must be drained
from the system before it will be permitted to start. The value is measured in minutes.
5.
Oil Pump Compressor Allowed Start Timer
This parameter is used to select the period of time within which the oil pump may run and the compressor is
still permitted to start. If this time period is exceeded, the oil must be drained before the compressor may
start. The value is measured in seconds.
6.
Oil Pump Prelube Timer
This parameter is used to select the period of time that the oil pump will run before the compressor is
started. This parameter is not used on Grasso compressors. The value is measured in seconds.
7.
Oil Pump Postlube Timer
This parameter is used to select the period of time that the oil pump will remain running after the compressor
has stopped. This parameter is not used on Grasso compressors. The value is measured in seconds.
8.
Oil Pump Run Minimum Timer
This parameter is used to select the minimum amount of time that the oil pump must run when it is started
based on low differential pressure. It will only appear if the oil pump type is set to
External Cycling
in the
configuration. The value is measured in seconds.
9.
Oil Pump Cycle On
This parameter is used to select the oil differential above which the oil pump will start. It will only appear if
the oil pump type is set to
External Cycling
in the configuration. The value is measured in seconds.
10.
Oil Pump Cycle Off
This parameter is used to select the oil differential below which the oil pump will stop after the time period
defined by the
Oil Pump Run Minimum Timer
haselapsed. It will only appear if the oil pump type is set to
External Cycling
in the configuration. The value is measured in seconds.
11.
Oil Pump Lead Selection
This parameter is used to select whether
Pump 1
or
Pump 2
is considered the lead pump. This parameter is
only visible if the
Dual Oil Pump
option is selected in the
Oil System Details
section of the configuration. The
options are:
•
Pump 1
•
Pump 2
12.
Oil Pump Maintained Timer
This parameter is used to select the period of time during startup that the oil pump must maintain a valid oil
differential pressure value before the compressor will be permitted to start. This parameter is fixed on
Grasso compressors and will not be visible. The value is measured in seconds.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
124
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016